Engineered for streamlined panel setups, the Phoenix Contact UNO-PS/1AC/12DC/100W power supply unit converts line voltage into reliable 12V DC power. Standard power supplies are essential for driving automation logic and field sensors safely.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC
- 1st secondary output voltage (EF006792): 12 V
- Max. output current 1 (EF008284): 8.3 A
- Secondary voltage adjustable (EF007002): No
- Nominal value output voltage 1 (EF009393): 12 V
- Nominal value output current 1 (EF009396): 8.3 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 85 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 210.8 VA
- Power output (EF003034): 100 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
More info
▲Key Commercial Data
| Orderkey | 2902997 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 229 (C-4-2017) |
| GTIN | 4046356808354 |
| Weight per Piece (excluding packing) | 340.000 g |
| Custom tariff number | 85044030 |
| Country of origin | PL (Poland) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| Input voltage range | 85 V AC ... 264 V AC |
| Current consumption | 2.19 A (100 V AC) |
| 1.13 A (240 V AC) | |
| Nominal power consumption | 210.8 VA |
| Inrush surge current | < 30 A (typical) |
| Mains buffering | typ. 20 ms (120 V AC) |
| typ. 85 ms (230 V AC) | |
| Input fuse | 4 A (slow-blow, internal) |
| Choice of suitable circuit breakers | 6 A ... 16 A (Characteristics B, C, D, K) |
| Power factor (cos phi) | 0.53 |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 12 V DC ±1 % |
|---|---|
| Nominal output current (IN) | 8.3 A (-25 °C ... 55 °C) |
| Derating | 55 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | < 25 V DC |
| Output overvoltage protection | ≤ 25 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 75 mVPP(with nominal values) |
| Output power | 100 W |
| Typical response time | < 1 s |
| Maximum power dissipation in no-load condition | < 0.4 W |
| Power loss nominal load max. | < 12 W |
General
| Net weight | 0.34 kg |
|---|---|
| Efficiency | typ. 88 % (120 V AC) |
| typ. 89 % (230 V AC) | |
| Insulation voltage input/output | 4 kV AC (type test) |
| 3 kV AC (routine test) | |
| Protection class | II (in closed control cabinet) |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 500000 h (40 °C) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 10 kHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standards/regulations | EN 61000-4-11 |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Safety of transformers | EN 61558-2-16 |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | EN 61000-4-11 |
| Information technology equipment - safety (CB scheme) | CB Scheme |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |