View larger
QUINT-PS/96-110DC/24DC/10 2905010 PHOENIX CONTACT DC/DC converters
QUINT-PS/96-110DC/24DC/10
2905010
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
QUINT-PS/96-110DC/24DC/10 2905010 PHOENIX CONTACT DC/DC converters function as specialized power conversion units that step direct current voltages up or down to match specific requirements within industrial control setups. DC/DC converters ensure proper voltage matching and isolation between different parts of an automated system.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): DC
- 1st secondary output voltage (EF006792): 18 V
- Max. output current 1 (EF008284): 12.5 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 10 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage DC (EF007078): 67.2 V
- Output voltage stabilized (EF003092): Yes
- Power output (EF003034): 240 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
- Modular version (EF001126): No
- Built-in height (EF000332): 130 mm
More info
▲Key Commercial Data
| Orderkey | 2905010 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 253 (C-4-2017) |
| GTIN | 4046356908313 |
| Weight per Piece (excluding packing) | 1,143.000 g |
| Custom tariff number | 85044030 |
| Country of origin | CN (China) |
Dimensions
| Width | 48 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 51 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Nominal input voltage range | 96 V DC ... 110 V DC |
|---|---|
| Input voltage range | 67.2 V DC ... 154 V DC |
| Current consumption | 3.5 A (96 V DC) |
| 3.1 A (110 V DC) | |
| Inrush surge current | < 10 A (typical) |
| Mains buffering | typ. 10 ms (96 V DC) |
| Input fuse | 10 A 150 V DC (internal (device protection)) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A (-40 °C ... 60 °C) |
| POWER BOOST (IBoost) | 12.5 A (-40°C ... 40°C permanent, UOUT= 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | 35 V DC |
| Output overvoltage protection | < 35 V DC |
| Max. capacitive load | unlimited |
| Active current limitation | 18 A |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 20 mVPP |
| Peak switching voltages nominal load | < 10 mVPP(20 MHz) |
| Maximum power dissipation in no-load condition | 4 W (UIN110 V DC) |
| Power loss nominal load max. | 22 W (UIN110 V DC) |
General
| Net weight | 0.9 kg |
|---|---|
| Efficiency | > 92 % (UIN96 V DC / UOUT24 V DC) |
| > 92 % (UIN110 V DC / UOUT24 V DC) | |
| Insulation voltage input/output | 1.5 kV (type test) |
| 1 kV (routine test) | |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 1357000 h (25 °C) |
| > 772000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |