View larger
RIF-3-RPT-LV-230AC/3X21 2903292 PHOENIX CONTACT Relay Module
RIF-3-RPT-LV-230AC/3X21
2903292
PHOENIX CONTACT
5 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The RIF-3-RPT-LV-230AC/3X21 2903292 PHOENIX CONTACT Relay Module from Phoenix Contact functions as an electromechanical switching device used in industrial control panels to isolate control circuits from load circuits and handle moderate electrical loads. Relay modules provide reliable signal multiplication and galvanic separation across complex automation architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Relay Module
- Product family: RIFLINE complete
- Application: Universal
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Date of last data management: 22.08.2024
- Article revision: 07
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: III
- Pollution degree: 2
- Maximum power dissipation for nominal condition: 3 W
- Test voltage (Winding/contact): 2.5 kV rms (50 Hz, 1 min., winding/contact)
- Test voltage (Contact/contact): 2 kV rms (50 Hz, 1 min., contact/contact)
- Rated insulation voltage: 250 V AC
- Rated surge voltage: 4 kV
- Coil side Nominal input voltage U N: 230 V AC
More info
▲| Product type | Relay Module |
| Product family | RIFLINE complete |
| Application | Universal |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Date of last data management | 22.08.2024 |
| Article revision | 07 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 3 W |
| Test voltage (Winding/contact) | 2.5 kVrms(50 Hz, 1 min., winding/contact) |
| Test voltage (Contact/contact) | 2 kVrms(50 Hz, 1 min., contact/contact) |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV |
| Coil side | |
| Nominal input voltage UN | 230 V AC |
| Input voltage range | 195.5 V AC ... 253 V AC (20 °C) |
| Input voltage range in reference to UN | see diagram |
| Mains frequency | 50/60 Hz |
| Drive and function | monostable |
| Drive (polarity) | polarized |
| Typical input current at UN | 13 mA |
| Typical response time | 5 ms ... 15 ms |
| Typical release time range | 5 ms ... 20 ms |
| Coil voltage | 230 V AC |
| Protective circuit | Varistor |
| Operating voltage display | Yellow LED |
| Switching | |
| Contact switching type | 3 changeover contacts |
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 10 V (24 mA) |
| Limiting continuous current | 6 A (see diagram) |
| Maximum inrush current | 30 A (20 ms, N/O contacts) |
| Min. switching current | 10 mA (24 V) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC) |
| 124 W (48 V DC) | |
| 108 W (60 V DC) | |
| 52 W (110 V DC) | |
| 48 W (220 V DC) | |
| 1500 VA (250 V AC) | |
| Utilization category CB Scheme (IEC 60947-5-1) | AC15, 1.5 A/240 V (N/O contact) |
| DC13, 2 A/240 V (N/O contact) | |
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) | |
| 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block) | |
| Conductor cross section AWG | 26 ... 16 (solid) |
| 26 ... 16 (flexible) |
| Drill hole | |
| Diameter | 3.2 mm |
| Width | 40 mm |
| Height | 103 mm |
| Depth | 90 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V2 (Housing) |
| Ambient conditions | |
| Degree of protection (Relay base) | IP20 (Relay base) |
| Degree of protection (Relay) | RT I (Relay) |
| Ambient temperature (operation) | -40 °C ... 50 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| Standards/regulations | IEC 60947-5-1 |
| Mounting type | DIN rail mounting |
| Assembly note | in rows with zero spacing |
| Mounting position | any |