View larger
RIF-1-RPT-LV-230AC/2X21MS 2905292 PHOENIX CONTACT Relay Module
RIF-1-RPT-LV-230AC/2X21MS
2905292
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact RIF-1-RPT-LV-230AC/2X21MS is a robust relay module designed for secure signal transmission and power amplification in control panels.
Industrial relay modules serve to link low-power PLC output channels directly to high-capacity actuators, motors, and valves while maintaining complete galvanic isolation throughout the system loop.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 184 V
- Rated control supply voltage AC 60 Hz (EF003979): 184 V
- Voltage type for actuating (EF008242): AC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.0035 A
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2905292 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 345 (C-5-2017) |
| GTIN | 4046356945387 |
| Weight per Piece (excluding packing) | 70.320 g |
| Custom tariff number | 85364900 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 45 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 230 V AC (50/60 Hz) |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Mains frequency | 50/60 Hz |
| Typical input current at UN | 3.5 mA |
| Typical response time | 4 ms ... 10 ms |
| Typical release time range | 3 ms ... 20 ms |
| Coil voltage | 230 V AC |
| Protective circuit | Varistor |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.81 W |
Contact side
| Contact type | 2 PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V (at 10 mA) |
| Min. switching current | 10 mA (at 12 V) |
| Maximum inrush current | 16 A (20 ms, N/O contact) |
| Limiting continuous current | see diagram |
| Interrupting rating (ohmic load) max. | 192 W (at 24 V DC) |
| 62 W (at 48 V DC) | |
| 42 W (at 60 V DC) | |
| 55 W (at 110 V DC) | |
| 66 W (at 220 V DC) | |
| 2000 VA (for 250 V AC) | |
| Switching capacity min. | 120 mW |
| Switching capacity | 1 A (at 24 V, DC13) |
| 1.5 A (at 230 V, AC15) |
Connection data 1
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) | |
| 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block) | |
| Conductor cross section AWG | 26 ... 16 (solid) |
| 26 ... 16 (flexible) |
Connection data 2
| Connection name | Contact side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| 0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve) | |
| 0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block) | |
| Conductor cross section AWG | 26 ... 16 (solid) |
| 26 ... 16 (flexible) |
General
| Test voltage relay winding/relay contact | 4 kVrms(50 Hz, 1 min.) |
|---|---|
| Test voltage PDT/PDT | 2.5 kVrms(50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | IP20 (Relay base) |
| RT II (Relay) | |
| Mechanical service life | approx. 5x 106cycles |
| Service life, electrical | see diagram |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 70.32 g |
Standards and Regulations
| Standards/regulations | DIN EN 50178 |
|---|---|
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | safe isolation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |