QUINT-PS/1AC/24DC/40 2866789 PHOENIX CONTACT Power supply unit
QUINT-PS/1AC/24DC/40
2866789
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact Power supply unit (QUINT-PS/1AC/24DC/40) functions as a heavy-duty switch-mode power supply engineered to deliver high-capacity direct current to demanding industrial setups. Industrial power supplies of this classification maintain stable output voltages under heavy electrical loads, protecting critical machinery and complex automation networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Voltage type (supply voltage) (EF002991): AC
- 1st secondary output voltage (EF006792): 18 V
- Max. output current 1 (EF008284): 45 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 40 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 85 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 90 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 1157 VA
- Power output (EF003034): 960 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
More info
▲Key Commercial Data
| Orderkey | 2866789 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 210 (C-4-2017) |
| GTIN | 4046356421720 |
| Weight per Piece (excluding packing) | 3,798.800 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 180 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 183 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | 4000 m |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 120 V DC ... 300 V DC (UL 508: ≤ 250 V DC) | |
| Input voltage range | 85 V AC ... 264 V AC |
| 90 V DC ... 300 V DC (UL 508: ≤ 250 V DC) | |
| Dielectric strength maximum | 300 V AC |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 8.8 A (120 V AC) |
| 4.6 A (230 V AC) | |
| 9.5 A (110 V DC) | |
| 4.7 A (220 V DC) | |
| Nominal power consumption | 1157 VA |
| Inrush surge current | < 15 A (typical) |
| Mains buffering | > 35 ms (120 V AC) |
| > 35 ms (230 V AC) | |
| Input fuse | 20 A (slow-blow, internal) |
| Choice of suitable circuit breakers | 16 A ... 20 A (AC: Characteristics B, C, D, K) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 40 A (-25 °C ... 60 °C, UOUT= 24 V DC) |
| POWER BOOST (IBoost) | 45 A (-25°C ... 40°C permanent, UOUT= 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 215 A (12 ms) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | max. 35 V DC |
| Output overvoltage protection | < 35 V DC |
| Residual ripple | < 30 mVPP(with nominal values) |
| Output power | 960 W |
| Typical response time | < 0.7 s |
| Maximum power dissipation in no-load condition | 14 W |
| Power loss nominal load max. | 80 W |
General
| Net weight | 3.3 kg |
|---|---|
| Efficiency | > 92 % (for 230 V AC and nominal values) |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage input / PE | 3.5 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage output / PE | 500 V DC (routine test) |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 900000 h (25 °C) |
| > 530000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 14 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 8 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 10 |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CSA |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| DIN VDE 0106-101 | |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard - Equipment safety | BG (design tested) |
| Shipbuilding approval | DNV GL (EMC A), ABS, LR, RINA, NK, BV |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Information technology equipment - safety (CB scheme) | CB Scheme |
| Rail applications | EN 50121-4 |
| Overvoltage category (EN 62477-1) | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |