View larger
QUINT-PS/1AC/24DC/10/CO 2320911 PHOENIX CONTACT Power supply, with protective coating
QUINT-PS/1AC/24DC/10/CO
2320911
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact QUINT-PS/1AC/24DC/10/CO power supply features a specialized protective coating designed to withstand corrosive atmospheres and moisture in demanding industrial plants. Conformal coating prevents circuit board degradation in chemical processing and marine environments. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2320911
- Packing unit: 1 pc
- Catalog page: Page 217 (C-4-2017)
- GTIN: 4046356520027
- Weight per Piece (excluding packing): 1,100.000 g
- Custom tariff number: 85044030
- Country of origin: TH (Thailand)
- Width: 60 mm
- Height: 130 mm
- Depth: 125 mm
- Width with alternative assembly: 122 mm
- Height with alternative assembly: 130 mm
- Depth with alternative assembly: 63 mm
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
- Ambient temperature (storage/transport): -40 °C ... 85 °C
More info
▲Key Commercial Data
| Orderkey | 2320911 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 217 (C-4-2017) |
| GTIN | 4046356520027 |
| Weight per Piece (excluding packing) | 1,100.000 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 60 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 63 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 100 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | 5000 m |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| 110 V DC ... 250 V DC | |
| Input voltage range | 85 V AC ... 264 V AC |
| 90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) | |
| Dielectric strength maximum | 300 V AC |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Discharge current to PE | < 3.5 mA |
| Current consumption | 2.2 A (120 V AC) |
| 1.3 A (230 V AC) | |
| 2.5 A (110 V DC) | |
| 1.2 A (220 V DC) | |
| Nominal power consumption | 303 VA |
| Inrush surge current | < 15 A |
| Mains buffering | typ. 36 ms (120 V AC) |
| typ. 36 ms (230 V AC) | |
| Input fuse | 10 A (slow-blow, internal) |
| Choice of suitable circuit breakers | 10 A ... 20 A (AC: Characteristics B, C, D, K) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor, gas-filled surge arrester |
Output data
| Nominal output voltage | 24 V DC ±1 % |
|---|---|
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A (-25 °C ... 60 °C, UOUT= 24 V DC) |
| POWER BOOST (IBoost) | 15 A (-25°C ... 40°C permanent, UOUT= 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in parallel | Yes, for redundancy and increased capacity |
| Connection in series | yes |
| Feedback resistance | max. 35 V DC |
| Output overvoltage protection | < 32 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 50 mVPP(with nominal values) |
| Output power | 240 W |
| Typical response time | < 0.15 s |
| Maximum power dissipation in no-load condition | 9.1 W |
| Power loss nominal load max. | 22 W |
General
| Net weight | 1.1 kg |
|---|---|
| Efficiency | > 92.5 % (for 230 V AC and nominal values) |
| Insulation voltage input/output | 4 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage input / PE | 3.5 kV AC (type test) |
| 2 kV AC (routine test) | |
| Insulation voltage output / PE | 500 V DC (routine test) |
| Protection class | I |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | > 940000 h (25 °C) |
| > 530000 h (40 °C) | |
| > 230000 h (60 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 55011 (EN 55022) |
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CSA |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| Standard - Safe isolation | DIN VDE 0100-410 |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard - Equipment safety | BG (design tested) |
| Shipbuilding approval | DNV GL (EMC B), ABS, LR, RINA, NK, BV |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| DeviceNet approval | DeviceNet™ Power Supply Conformance Tested |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706 Compliance Certificate |
| Information technology equipment - safety (CB scheme) | IEC 60950-1 (2ndEdition) |
| Rail applications | EN 50121-4 |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| ATEX | II 3 G Ex nA nC IIC T4 Gc |
| TÜV 11 ATEX 079480 X | |
| IECEx | Ex nA nC IIC T4 Gc |
| IECEx TUN 11.0007X | |
| Overvoltage category (EN 62477-1) | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |