View larger
MINI-BAT/12DC/2.6AH 2866569 PHOENIX CONTACT Energy storage
MINI-BAT/12DC/2.6AH
2866569
PHOENIX CONTACT
1 Pcs.
Automation > Battery (lithium) for vehicles and applications
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact MINI-BAT/12DC/2.6AH energy storage provides reliable backup power for industrial control systems during unexpected grid interruptions. Energy storage units are typically integrated into DC power supply networks to maintain critical operations and prevent data loss in automation hardware. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Input voltage: 12 V DC
- Buffer period: 120 min. (1 A)
- Current consumption: 0.72 A (charging process)
- Nominal output voltage: 12 V DC
- Output current I max: 15 A
- Output fuse: 1x 15 A
- Connection in parallel: 5
- Connection in series: no
- Battery operation Nominal output voltage: 12 V DC
- Nominal output current (I N ): 15 A
- End-of-charge voltage: 13.8 V
- Charging current: 0.72 A
- Nominal capacity: 2.4 Ah
- Battery module service life: 6 Years (20 °C)
- Latest startup (battery only) - range: 6 Months (0 °C ... 20 °C)
- Battery technology: VRLA-AGM
More info
▲| General | |
| Note on the battery | This product contains a battery with a limited shelf life that must be charged every few months. The product packaging indicates when the battery must be started up or recharged. The general shelf life can be found in the technical data area under “Latest startup”. |
| Input voltage | 12 V DC |
| Buffer period | 120 min. (1 A) |
| 20 min. (4 A) | |
| Current consumption | 0.72 A (charging process) |
| Nominal output voltage | 12 V DC |
| Output current Imax | 15 A |
| Output fuse | 1x 15 A |
| Connection in parallel | 5 |
| Connection in series | no |
| Battery operation | |
| Nominal output voltage | 12 V DC |
| Nominal output current (IN) | 15 A |
| End-of-charge voltage | 13.8 V |
| Charging current | 0.72 A |
| Nominal capacity | 2.4 Ah |
| Battery module service life | 6 Years (20 °C) |
| Latest startup (battery only) - range | 6 Months (0 °C ... 20 °C) |
| 6 Months (20 °C ... 30 °C) | |
| 3 Months (30 °C ... 40 °C) | |
| Battery technology | VRLA-AGM |
| Memory medium | Lead rechargeable battery module |
| Accumulator type | BB Battery BP1.2-12FR |
| Number of cells | 1 |
| Size designation | Block |
| Battery pack | yes |
| IQ technology | no |
| Suitable for fast charging | yes |
| Product type | Battery module |
| Product family | Battery module |
| Application | for MINI DC-UPS |
| Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
| IQ technology | no |
| Data management status | |
| Article revision | 04 |
| Insulation characteristics | |
| Protection class | III |
| Width | 52 mm |
| Height | 130 mm |
| Depth | 110 mm |
| Installation dimensions | |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 30 mm / 30 mm |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | 0 °C ... 40 °C |
| Ambient temperature (storage/transport) | 0 °C ... 40 °C |
| Max. permissible relative humidity (operation) | 95 % |
| Suited for EX-applications | no |