View larger
DEK-OV- 5DC/240AC/800 2964623 PHOENIX CONTACT Solid-state relay terminal block
DEK-OV-5DC/240AC/800
2964623
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The DEK-OV- 5DC/240AC/800 2964623 PHOENIX CONTACT Solid-state relay terminal block acts as an interface component designed to switch higher-voltage AC loads using standard low-voltage logic outputs. Solid-state terminal blocks eliminate moving parts, ensuring silent operation, high switching frequencies, and extended lifespans in industrial control loops. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 4 V
- Type of voltage (input voltage) (EF003033): DC
- Output voltage (EF003933): 10 V
- Type of output voltage (EF008222): AC
- Rated operation current Ie (EF001443): 0.8 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2964623 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 441 (C-5-2017) |
| GTIN | 4017918130909 |
| Weight per Piece (excluding packing) | 21.070 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 5 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 4 V DC ... 6 V DC |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
| Typical input current at UN | 10.2 mA |
| Typical response time | < 10 ms |
| Typical turn-off time | < 10 ms |
| Operating voltage display | Yellow LED |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Protective circuit/component | Polarity protection diode |
| Transmission frequency | 10 Hz |
Output data
| Output voltage range | 10 V AC ... 253 V AC (50/60 Hz) |
|---|---|
| Limiting continuous current | 0.8 A (see derating curve) |
| Maximum inrush current | 30 A (t = 10 ms) |
| Min. load current | 10 mA |
| Leakage current | 1.2 mA |
| Surge current | 30 A (t = 10 ms) |
| Max. load value | 4.5 A2s |
| Peak offstate voltage | 600 V (Periodic peak reverse voltage) |
| Voltage drop at max. limiting continuous current | ≤ 1 V |
| Output circuit | 2-conductor floating, zero voltage switch |
| Type of protection | RCV circuit |
| Protective circuit/component | RCV circuit |
Connection data, input side
| Connection name | Input side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Torque | 0.5 Nm |
Connection data, output side
| Connection name | Output side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Torque | 0.5 Nm |
General
| Note | The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949). |
|---|---|
| Type of note | Note on application |
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage input/output | 2.5 kV AC |
| 2.5 kV (50 Hz, 1 min.) | |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Degree of pollution | 2 |
| Overvoltage category | III |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |