DEK-OV- 24DC/ 24DC/ 10 2964322 PHOENIX CONTACT Solid-state relay terminal block
DEK-OV-24DC/ 24DC/ 10
2964322
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact DEK-OV-24DC/ 24DC/ 10 functions as a solid-state relay terminal block built to handle higher current operational loads in factory automation environments. Terminal relays provide reliable, bounce-free electronic switching to interface control electronics directly with heavier industrial actuators.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 19.2 V
- Type of voltage (input voltage) (EF003033): DC
- Output voltage (EF003933): 8 V
- Type of output voltage (EF008222): DC
- Rated operation current Ie (EF001443): 10 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2964322 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 441 (C-5-2017) |
| GTIN | 4017918893194 |
| Weight per Piece (excluding packing) | 25.500 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
| Typical input current at UN | 3.5 mA |
| Typical response time | 250 µs |
| Typical turn-off time | 800 µs |
| Operating voltage display | Yellow LED |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Transmission frequency | 100 Hz |
| Power dissipation for nominal condition | 0.5 W |
Output data
| Output voltage range | 5 V DC ... 30 V DC |
|---|---|
| Limiting continuous current | 10 A (see derating curve) |
| Surge current | 100 A (t = 20 ms) |
| Voltage drop at max. limiting continuous current | ≤ 50 mV |
| Output circuit | 3-conductor, ground-referenced |
| Type of protection | Reverse polarity protection |
| Surge protection |
Connection data, input side
| Connection name | Input side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Connection data, output side
| Connection name | Output side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
General
| Note | The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949). |
|---|---|
| Type of note | Note on application |
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage input/output | 2.5 kV AC |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Degree of pollution | 2 |
| Overvoltage category | II |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |