View larger
DEK-OV- 12DC/ 24DC/ 3 2941387 PHOENIX CONTACT Solid-state relay terminal block
DEK-OV-12DC/ 24DC/ 3
2941387
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for space-saving panel installations, the DEK-OV-12DC/ 24DC/ 3 2941387 PHOENIX CONTACT Solid-state relay terminal block provides efficient galvanic isolation for DC control loops. Industrial terminal blocks safeguard downstream components from electrical feedback and surges, maintaining optimal system uptime across automated production lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 9.6 V
- Type of voltage (input voltage) (EF003033): DC
- Output voltage (EF003933): 3 V
- Type of output voltage (EF008222): AC
- Rated operation current Ie (EF001443): 3 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2941387 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 441 (C-5-2017) |
| GTIN | 4017918080402 |
| Weight per Piece (excluding packing) | 21.600 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Input data
| Nominal input voltage UN | 12 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 9.6 V DC ... 14.4 V DC |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
| Typical input current at UN | 8.5 mA |
| Typical response time | 40 µs |
| Typical turn-off time | 200 µs |
| Operating voltage display | Yellow LED |
| Type of protection | Reverse polarity protection |
| Transmission frequency | 300 Hz |
| Power dissipation for nominal condition | 0.1 W |
Output data
| Output voltage range | 3 V DC ... 30 V DC |
|---|---|
| Limiting continuous current | 3 A (see derating curve) |
| Voltage drop at max. limiting continuous current | ≤ 0.2 V |
| Output circuit | 2-wire, floating |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Protective circuit/component | Polarity protection diode |
Connection data, input side
| Connection name | Input side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Connection data, output side
| Connection name | Output side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
General
| Type of note | Note on application |
|---|---|
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage input/output | 2.5 kV AC |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Degree of pollution | 2 |
| Overvoltage category | III |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |