PHOENIX CONTACT FTRV 4-PV BU/BK FTRV 4-PV BU/BK 3270181 PHOENIX CONTACT Potential distributors View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FTRV 4-PV BU/BK 3270181 PHOENIX CONTACT Potential distributors

FTRV 4-PV BU/BK

3270181

PHOENIX CONTACT

10 Pcs.

Potential distributors Potential distributor, without drive compressor, nominal voltage: 250 V, nominal current: 17.5 A, connection type: Push-in connection, 1., 2., 3. and 4th floor, Dimensioning section: 1.5 mm², cross-section: 0.14 mm² - 2.5 mm², mounting: NS 35/7.5, NS 35/15, color: blue, connection element color: black

Automation > Feed-through terminal block
Enclosures connectivity

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact FTRV 4-PV BU/BK is a potential distributor designed to organize and distribute common electrical potentials within high-density control cabinets. Multi-level distributor blocks help streamline complex wiring systems by grouping related circuits together. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 3270181
  • Packing unit: 10 pc
  • Minimum order quantity: 10 pc
  • Note: Made to Order (non-returnable)
  • Catalog page: Page 45 (C-1-2017)
  • GTIN: 4046356796323
  • Weight per Piece (excluding packing): 16.710 g
  • Custom tariff number: 85369010
  • Country of origin: PL (Poland)
  • Number of positions: 2
  • Number of levels: 4
  • Number of connections: 16
  • Potentials: 1
  • Nominal cross section: 1.5 mm²
  • Color: blue
  • Color of connection elements: black

More info

▲

Key Commercial Data

Orderkey3270181
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 45 (C-1-2017)
GTIN4046356796323
Weight per Piece (excluding packing)16.710 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of positions2
Number of levels4
Number of connections16
Potentials1
Nominal cross section1.5 mm²
Colorblue
Color of connection elementsblack
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage4 kV
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.56 W (the value is multiplied when connecting multiple levels)
Maximum load current20 A (in case of a 2.5 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal current IN17.5 A
Nominal voltage UN250 V
Open side panelYes
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint4.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.5 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.14 mm² / 0.2 kg
1.5 mm² / 0.4 kg
2.5 mm² / 0.7 kg
Tensile test resultTest passed
Conductor cross section tensile test0.14 mm²
Tractive force setpoint10 N
Conductor cross section tensile test1.5 mm²
Tractive force setpoint40 N
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 6,4 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing1.5 mm²
Short-time current0.18 kA
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Result of thermal testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width8.3 mm
Length64 mm
Height NS 35/7,555.5 mm
Height NS 35/1563 mm

Connection data

Connection methodPush-in connection
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible26
Max. AWG conductor cross section, flexible14
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.1.5 mm²

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.