View larger
REL-MR-110DC/21HC 2961338 PHOENIX CONTACT Single relay
REL-MR-110DC/21HC
2961338
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact REL-MR-110DC/21HC single relay functions as an electromechanical switching element designed to isolate control circuits from load circuits in industrial automation networks. Such components are commonly integrated into control cabinets to handle high operating currents and provide reliable signal multiplication across various automation machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Single relay
- Operating mode: 100% operating factor
- Mechanical service life: 3x 10 7 cycles
- Data management status Date of last data management: 02.05.2024
- Article revision: 02
- Insulation characteristics Overvoltage category: III
- Pollution degree: 3
- Service life electrical: see diagram
- Maximum power dissipation for nominal condition: 0.45 W
- Test voltage (Winding/contact): 5 kV AC (50 Hz, 1 min., winding/contact)
- Coil side Nominal input voltage U N: 110 V DC
- Input voltage range: 71.5 V DC ... 264 V DC
- Drive and function: monostable
- Drive (polarity): non-polarized
- Typical input current at U N: 4.1 mA
- Typical response time: 7 ms
More info
▲| Product type | Single relay |
| Operating mode | 100% operating factor |
| Mechanical service life | 3x 107cycles |
| Data management status | |
| Date of last data management | 02.05.2024 |
| Article revision | 02 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 3 |
| Service life electrical | see diagram |
| Maximum power dissipation for nominal condition | 0.45 W |
| Test voltage (Winding/contact) | 5 kV AC (50 Hz, 1 min., winding/contact) |
| Coil side | |
| Nominal input voltage UN | 110 V DC |
| Input voltage range | 71.5 V DC ... 264 V DC |
| Drive and function | monostable |
| Drive (polarity) | non-polarized |
| Typical input current at UN | 4.1 mA |
| Typical response time | 7 ms |
| Typical release time | 3 ms |
| Coil resistance | 26600 Ω ±15 % (at 20 °C) |
| Switching | |
| Contact switching type | 1 changeover contact |
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V (at 10 mA) |
| Limiting continuous current | 16 A |
| Maximum inrush current | 50 A (20 ms) |
| Min. switching current | 10 mA (at 12 V) |
| Interrupting rating (ohmic load) max. | 384 W (at 24 V DC) |
| 58 W (at 48 V DC) | |
| 48 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 80 W (at 220 V DC) | |
| 4000 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 0.2 A (at 110 V, DC13) | |
| 0.2 A (at 250 V, DC13) | |
| 6 A (at 24 V, AC15) | |
| 6 A (at 120 V, AC15) | |
| 6 A (at 250 V, AC15) | |
| Motor load according to UL 508 | 1/2 HP, 120 V AC (N/O contact) |
| 1 HP, 240 V AC (N/O contact) | |
| 1/3 HP, 120 V AC (N/C contact) | |
| 3/4 HP, 240 V AC (N/C contact) | |
| 1/4 HP, 200 ... 250 V AC | |
| Connection method | Plug / solder connection |
| Dimensional drawing | |
| Width | 12.7 mm |
| Height | 29 mm |
| Depth | 15.7 mm |
| Color | white (RAL 9010) |
| Ambient conditions | |
| Degree of protection | RT II |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| EN 61810-1 |
| Assembly note | Can be aligned without spacing (> 70 °C ≥ 2.5 mm) |
| Mounting position | any |