View larger
SP 2,5/ 1-L 3043019 PHOENIX CONTACT Plug
SP 2,5/ 1-L
3043019
PHOENIX CONTACT
50 Pcs.
Connectors > Terminal block connector
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact SP 2,5/ 1-L Plug functions as a dependable modular terminal connector configured to handle routine signal and power transmission duties in automated systems. Pluggable terminal blocks streamline maintenance operations by permitting quick disconnection of specific circuits without disturbing adjacent wiring.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Terminal plug
- Number of positions: 1
- Pitch: 5.2 mm
- Data management status Article revision: 03
- Insulation characteristics Overvoltage category: III
- Degree of pollution: 3
- Rated surge voltage: 6 kV
- Nominal cross section: 2.5 mm²
- Stripping length: 8 mm ... 10 mm
- Internal cylindrical gage: A3
- Connection in acc. with standard: IEC 61984
- Conductor cross section rigid: 0.08 mm² ... 4 mm²
- Cross section AWG: 28 ... 12 (converted acc. to IEC)
- Conductor cross section flexible: 0.08 mm² ... 2.5 mm²
- Conductor cross section, flexible [AWG]: 28 ... 14 (converted acc. to IEC)
- Nominal current: 24 A
More info
▲| Product type | Terminal plug |
| Number of positions | 1 |
| Pitch | 5.2 mm |
| Data management status | |
| Article revision | 03 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Rated surge voltage | 6 kV |
| Nominal cross section | 2.5 mm² |
| Stripping length | 8 mm ... 10 mm |
| Internal cylindrical gage | A3 |
| Connection in acc. with standard | IEC 61984 |
| Conductor cross section rigid | 0.08 mm² ... 4 mm² |
| Cross section AWG | 28 ... 12 (converted acc. to IEC) |
| Conductor cross section flexible | 0.08 mm² ... 2.5 mm² |
| Conductor cross section, flexible [AWG] | 28 ... 14 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² |
| Nominal current | 24 A |
| Maximum load current | 24 A (with 4 mm² conductor cross section) |
| Nominal voltage | 500 V |
| Nominal cross section | 2.5 mm² |
| Width | 5.2 mm |
| Height | 15.8 mm |
| Depth | 39 mm |
| Length | 15.8 mm |
| Pitch | 5.2 mm |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static insulating material application in cold | -60 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C (max. operating temperature see derating curve) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (operation) | 20 % ... 90 % |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Connection in acc. with standard | IEC 61984 |