Prevent electrical damage in automation control panels by deploying the Phoenix Contact VAL-SEC-T2-2C-350 type 2 surge arrester. These protection units act swiftly during voltage anomalies to divert harmful energy away from critical instrumentation, maintaining high reliability across industrial networks.
Please note that pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- System configuration IT (EF009927): No
- System configuration TN (EF009928): No
- System configuration TN-C (EF009929): Yes
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): No
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Nominal discharge surge current (8/20) (EF004214): 20 kA
- Max. discharge surge current (8/20) (EF012274): 40 kA
- Max. continuous voltage AC (EF004198): 350 V
- Voltage protection level L-N (EF004236): 1.5 kV
- Short-circuit breaking capacity (Isccr) (EF012627): 50 kA
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Key Commercial Data
| Orderkey | 2905342 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 47 (C-4-2017) |
| GTIN | 4046356948265 |
| Weight per Piece (excluding packing) | 225.000 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-C |
| Mode of protection | L-PEN |
| Mounting type | DIN rail: 35 mm |
| Color | light grey RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240/415 V AC (TN-C) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 350 V AC |
| Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
| 63 A (TWIN ferrule 2 x 10 mm²) | |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA (in case of 315 A gG backup fuse) |
| 50 kA (in case of 200 A gG backup fuse) | |
| Voltage protection level Up | ≤ 1.5 kV |
| Residual voltage Ures | ≤ 1.5 kV (at In) |
| ≤ 1.3 kV (at 10 kA) | |
| ≤ 1.2 kV (at 5 kA) | |
| ≤ 1.1 kV (at 4 kA) | |
| ≤ 1 kV (at 2 kA) | |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
| 63 A (gG / TWIN ferrule 2x 10mm²) | |
| Max. backup fuse with branch wiring | 315 A (gG) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 16 mm² |
| Conductor cross section solid | 2.5 mm² ... 25 mm² |
| Conductor cross section AWG | 12 ... 4 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 6 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-L) | 700 V AC |
| Maximum continuous operating voltage MCOV (L-N) | 350 V AC |
| Nom. voltage | 277/480 V AC |
| Mode of protection | L-L |
| L-N | |
| Power distribution system | Wye |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-L) | 3280 V |
| Measured limiting voltage MLV (L-N) | 2000 V |
| Nominal discharge current In(L-L) | 20 kA |
| Nominal discharge current In(L-N) | 20 kA |
UL connection data
| Conductor cross section AWG | 14 ... 2 (solid) |
|---|---|
| 14 ... 4 (flexible) | |
| Tightening torque | 40 lbf-in. ... 50 lbf-in. |