PHOENIX CONTACT VAL-SEC-T2-1S-175-FM VAL-SEC-T2-1S-175-FM 2905348 VAL‐CP‐1S‐175 2859479 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-1S-175-FM 2905348 VAL‐CP‐1S‐175 2859479 PHOENIX CONTACT Type 2 surge arrester

VAL-SEC-T2-1S-175-FM

2905348

VAL‐CP‐1S‐175 2859479

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Plug-in surge charger according to type 2/class II, for single-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The VAL-SEC-T2-1S-175-FM 2905348 VAL‐CP‐1S‐175 2859479 PHOENIX CONTACT Type 2 surge arrester is an advanced protective device built to mitigate transient voltage surges in industrial electrical grids. This component is typically installed in main or sub-distribution boards to safeguard sensitive automation hardware from electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2905348
  • Packing unit: 1 pc
  • Catalog page: Page 49 (C-4-2017)
  • GTIN: 4046356948036
  • Weight per Piece (excluding packing): 207.800 g
  • Custom tariff number: 85363030
  • Country of origin: DE (Germany)
  • Height: 97.9 mm
  • Width: 25.4 mm
  • Depth: 74.5 mm (incl. DIN rail 7.5 mm)
  • Horizontal pitch: 1.4 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 2000 m (amsl (above mean sea level))
  • Permissible humidity (operation): 5 % ... 95 %

More info

▲

Key Commercial Data

Orderkey2905348
Packing unit1 pc
Catalog pagePage 49 (C-4-2017)
GTIN4046356948036
Weight per Piece (excluding packing)207.800 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height97.9 mm
Width25.4 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1.4 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorlight grey RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN120 V AC (TN-S)
120 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)175 V AC
Maximum continuous operating voltage UC(L-PE)175 V AC
Maximum continuous voltage UC(N-PE)150 V AC
Rated load current IL40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Follow current interrupt rating Ifi(N-PE)100 A (150 V AC)
Short-circuit current rating ISCCR25 kA (in case of 315 A gG backup fuse)
50 kA (in case of 200 A gG backup fuse)
Voltage protection level Up(L-N)≤ 0.85 kV
Voltage protection level Up(L-PE)≤ 1.3 kV
Voltage protection level Up(N-PE)≤ 0.95 kV
Residual voltage Ures(L-N)≤ 0.85 kV (at In)
≤ 0.75 kV (at 10 kA)
≤ 0.65 kV (at 5 kA)
≤ 0.63 kV (at 4 kA)
≤ 0.57 kV (at 2 kA)
Residual voltage Ures(N-PE)≤ 0.4 kV (at In)
≤ 0.4 kV (at 10 kA)
≤ 0.4 kV (at 5 kA)
≤ 0.4 kV (at 4 kA)
≤ 0.4 kV (at 2 kA)
TOV behavior at UT(L-N)240 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA(L-N)≤ 25 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with V-type through wiring40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring315 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 6 mm²

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)175 V AC
Maximum continuous operating voltage MCOV (L-G)175 V AC
Maximum continuous operating voltage MCOV (N-G)150 V AC
Nom. voltage120 V AC
Mode of protectionL-N
L-G
N-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1510 V
Measured limiting voltage MLV (L-G)1630 V
Measured limiting voltage MLV (N-G)560 V
Nominal discharge current In(L-N)20 kA
Nominal discharge current In(L-G)20 kA
Nominal discharge current In(N-G)20 kA

UL indicator/remote signaling

Operating voltage125 V AC
Operating current1 A AC
Tightening torque2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG30 ... 14

UL connection data

Conductor cross section AWG14 ... 2 (solid)
14 ... 4 (flexible)
Tightening torque40 lbf-in. ... 50 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.