View larger
OPT-24DC/230AC/ 2 2982171 PHOENIX CONTACT Miniature solid-state relay
OPT-24DC/230AC/ 2
2982171
PHOENIX CONTACT
10 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built for high-density space allocations in electrical control panels, the OPT-24DC/230AC/ 2 2982171 PHOENIX CONTACT Miniature solid-state relay provides reliable electronic switching and signal isolation. These compact relays bridge low-level logic signals and heavier field loads without generating mechanical contact wear. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 19.2 V
- Type of voltage (input voltage) (EF003033): DC
- Output voltage (EF003933): 24 V
- Type of output voltage (EF008222): AC
- Rated operation current Ie (EF001443): 2 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): No
More info
▲Key Commercial Data
| Orderkey | 2982171 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Catalog page | Page 311 (C-5-2017) |
| GTIN | 4017918996970 |
| Weight per Piece (excluding packing) | 10.330 g |
| Custom tariff number | 85364190 |
| Country of origin | HU (Hungary) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| Switching threshold "0" signal, voltage | < 8.4 V DC |
| Switching threshold "1" signal voltage | > 18 V DC |
| Typical input current at UN | 7 mA |
| Typical response time | 10 ms |
| Typical turn-off time | 10 ms |
| Type of protection | Reverse polarity protection |
| Protective circuit/component | Polarity protection diode |
| Transmission frequency | 10 Hz |
| Power dissipation for nominal condition | 0.17 W |
Output data
| Output nominal voltage | 230 V AC |
|---|---|
| Output voltage range | 24 V AC ... 253 V AC |
| Limiting continuous current | 2 A (see derating curve) |
| Maximum inrush current | 30 A (10 ms) |
| Min. load current | 25 mA |
| Leakage current | typ. 1 mA |
| Surge current | 30 A (10 ms) |
| Max. load value | 4 A2s (tp = 10 ms, at 25 °C) |
| Voltage drop at max. limiting continuous current | ≤ 1 V |
| Output circuit | 2-conductor floating, zero voltage switch |
| Type of protection | Surge protection |
| Protective circuit/component | RC element |
General
| Test voltage input/output | 2.5 kV (50 Hz, 1 min.) |
|---|---|
| Mounting position | any |
| Assembly instructions | See derating curve |
| Operating mode | 100% operating factor |
| Degree of protection | RT III (wash-proof) |
| Flammability rating according to UL 94 | V0 |
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Degree of pollution | 2 |
| Overvoltage category | III |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Rated insulation voltage | 250 V AC |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |