View larger
REL-IR4/LDP-110DC/4X21AU 2903673 PHOENIX CONTACT Single relay
REL-IR4/LDP-110DC/4X21AU
2903673
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A REL-IR4/LDP-110DC/4X21AU 2903673 PHOENIX CONTACT Single relay serves as a high-reliability plug-in switching component, ideal for complex industrial control circuits requiring multiple isolated contact paths and gold-plated surfaces.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Plug-in connection
- Complete with socket (EF003359): No
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 88 V
- Voltage type for actuating (EF008242): DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 4
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Gold
- Nominal current (EF000001): 0.008 A
- Width (EF000008): 21.2 mm
More info
▲Key Commercial Data
| Orderkey | 2903673 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Catalog page | Page 314 (C-5-2017) |
| GTIN | 4046356758864 |
| Weight per Piece (excluding packing) | 34.340 g |
| Custom tariff number | 85364900 |
| Country of origin | PL (Poland) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 110 V DC |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Typical input current at UN | 8 mA |
| Typical response time | 13 ms |
| Typical release time | 14 ms |
| Protective circuit | Damping diode |
| Status display | Yellow LED |
| Power dissipation for nominal condition | 0.88 W |
Contact side
| Contact type | 4 PDTs |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi, hard gold-plated |
| Note | If the specified maximum values for multi-layer contact relays are exceeded, the gold plating is destroyed. The maximum values of the power contact relay are then valid. This can result in a shorter service life than with a pure power contact. |
| Maximum switching voltage | 30 V AC |
| 36 V DC | |
| Minimum switching voltage | 2 V (At 24 mA) |
| Min. switching current | 2 mA (24 V DC) |
| Maximum inrush current | 50 mA |
| Limiting continuous current | 50 mA |
| Interrupting rating (ohmic load) max. | 1.2 W (at 24 V DC) |
| Switching capacity min. | 48 mW |
| Motor load according to UL 508 | 1/3 HP, 240 V AC |
Contact side (with destroyed gold layer)
| Contact material | AgNi |
|---|---|
| Note | the following values are applicable if a gold layer is destroyed |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (At 24 mA) |
| Limiting continuous current | 6 A |
| Maximum inrush current | 16 A (20 ms, N/O contact) |
| Min. switching current | 5 mA (at 24 V) |
| Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
| 124 W (at 48 V DC) | |
| 108 W (at 60 V DC) | |
| 52 W (at 110 V DC) | |
| 48 W (at 220 V DC) | |
| 1500 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 0.22 A (at 120 V, DC13) | |
| 0.11 A (at 250 V, DC13) | |
| 1.5 A (at 24 V, AC15) | |
| 1.5 A (at 120 V, AC15) | |
| 1 A (at 240 V, AC15) |
General
| Test voltage relay winding/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
|---|---|
| Test voltage PDT/PDT | 2 kVrms(50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT I |
| Mechanical service life | approx. 2x 107cycles |
| Service life, electrical | see diagram |
| Mounting position | any |
| Net weight (SAP) | 34.34 g |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| Standards/regulations | IEC 60664 |
| IEC 61810 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 2.5 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |