View larger
Images are for illustrative purposes only. Please refer to data sheet for details
REL-PR3- 24AC/3X1 2903707 PHOENIX CONTACT Single relay
REL-PR3-24AC/3X1
2903707
PHOENIX CONTACT
1 Pcs.
Single relay
Plug-in high-power relays with power contacts, 3 open contacts, coil voltage: 24 V AC
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact REL-PR3- 24AC/3X1 single relay functions as a rugged switching device used to govern heavy industrial electrical loads and expand contact capacity within control gear. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection: Plug-in connection
- Complete with socket: No
- With detachable clamps: No
- With LED indication: No
- Rated control supply voltage AC 50 Hz: 20.4 V
- Rated control supply voltage AC 60 Hz: 20.4 V
- Voltage type for actuating: AC
- Drive, polarization: Polarity free
- Drive, switching attitude: Mono stable
- Number of contacts as normally closed contact: 0
- Number of contacts as normally open contact: 3
- Number of contacts as change-over contact: 0
- Type of switch contact: Single contact
- With forced-guided contacts: No
- Material of contact surface: Untreated
- Nominal current: 0.116 A
More info
▲Key Commercial Data
| Orderkey | 2903707 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 328 (C-5-2017) |
| GTIN | 4046356759199 |
| Weight per Piece (excluding packing) | 83.200 g |
| Custom tariff number | 85364190 |
| Country of origin | PL (Poland) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 24 V AC |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Mains frequency | 50/60 Hz |
| Typical input current at UN | 116 mA |
| Typical response time | 5 ms ... 25 ms (depending on phase relation) |
| Typical release time range | 5 ms ... 20 ms (depending on phase relation) |
| Power dissipation for nominal condition | 2.78 W |
Contact side
| Contact type | 3 N/O contacts |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 440 V AC |
| 250 V DC | |
| Minimum switching voltage | 10 V (At 24 mA) |
| Min. switching current | 10 mA (at 24 V) |
| Maximum inrush current | 50 A (20 ms, N/O contact) |
| Limiting continuous current | 16 A |
| Interrupting rating (ohmic load) max. | 384 W (at 24 V DC) |
| 720 W (at 48 V DC) | |
| 600 W (at 60 V DC) | |
| 660 W (at 110 V DC) | |
| 183 W (at 220 V DC) | |
| 4000 VA (for 250 V AC) | |
| 4000 VA (at 440 V AC) | |
| Switching capacity | 1 A (at 24 V, DC13) |
| 1 A (at 120 V, DC13) | |
| 1 A (at 220 V, DC13) | |
| 1.5 A (at 24 V, AC15) | |
| 1.5 A (at 120 V, AC15) | |
| 1.5 A (at 240 V, AC15) | |
| 3-phase motor load | 1500 W (at 400 V, AC3) |
| Motor load according to UL 508 | 1/3 HP, 120 V AC (N/O contact) |
| 1/2 HP, 240 V AC (N/O contact) |
General
| Test voltage relay winding/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
|---|---|
| Test voltage relay contact/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
| Test voltage N/O contact/N/O contact | 2.5 kVrms(50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT I |
| Mechanical service life | approx. 107cycles |
| Service life, electrical | see diagram |
| Mounting position | any |
| Net weight (SAP) | 83.2 g |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| Standards/regulations | IEC 60664 |
| IEC 61810 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV |
| Insulation | Basic insulation |
| Degree of pollution | 3 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |