View larger
REL-PR3-230AC/3X1 2903709 PHOENIX CONTACT Single relay
REL-PR3-230AC/3X1
2903709
PHOENIX CONTACT
1 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact single relay, referenced as REL-PR3-230AC/3X1, is engineered to handle higher-capacity switching duties within industrial power distribution and motor control architectures. Single relays provide discrete isolation pathways and reliable contact transfer for demanding automated operational sequences.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Plug-in connection
- Complete with socket (EF003359): No
- With detachable clamps (EF003340): No
- With LED indication (EF005950): No
- Rated control supply voltage AC 50 Hz (EF003978): 195.5 V
- Rated control supply voltage AC 60 Hz (EF003979): 195.5 V
- Voltage type for actuating (EF008242): AC
- Drive, polarization (EF003355): Polarity free
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 3
- Number of contacts as change-over contact (EF008257): 0
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.012 A
More info
▲Key Commercial Data
| Orderkey | 2903709 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 328 (C-5-2017) |
| GTIN | 4046356759212 |
| Weight per Piece (excluding packing) | 82.900 g |
| Custom tariff number | 85364900 |
| Country of origin | PL (Poland) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 230 V AC |
|---|---|
| Input voltage range in reference to UN | see diagram |
| Mains frequency | 50/60 Hz |
| Typical input current at UN | 12 mA |
| Typical response time | 5 ms ... 25 ms (depending on phase relation) |
| Typical release time range | 5 ms ... 20 ms (depending on phase relation) |
| Power dissipation for nominal condition | 2.76 W |
Contact side
| Contact type | 3 N/O contacts |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 440 V AC |
| 250 V DC | |
| Minimum switching voltage | 10 V (At 24 mA) |
| Min. switching current | 10 mA (at 24 V) |
| Maximum inrush current | 50 A (20 ms, N/O contact) |
| Limiting continuous current | 16 A |
| Interrupting rating (ohmic load) max. | 384 W (at 24 V DC) |
| 720 W (at 48 V DC) | |
| 600 W (at 60 V DC) | |
| 660 W (at 110 V DC) | |
| 183 W (at 220 V DC) | |
| 4000 VA (for 250 V AC) | |
| 4000 VA (at 440 V AC) | |
| Switching capacity | 1 A (at 24 V, DC13) |
| 1 A (at 120 V, DC13) | |
| 1 A (at 220 V, DC13) | |
| 1.5 A (at 24 V, AC15) | |
| 1.5 A (at 120 V, AC15) | |
| 1.5 A (at 240 V, AC15) | |
| 3-phase motor load | 1500 W (at 400 V, AC3) |
| Motor load according to UL 508 | 1/3 HP, 120 V AC (N/O contact) |
| 1/2 HP, 240 V AC (N/O contact) |
General
| Test voltage relay winding/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
|---|---|
| Test voltage relay contact/relay contact | 2.5 kVrms(50 Hz, 1 min.) |
| Test voltage N/O contact/N/O contact | 2.5 kVrms(50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT I |
| Mechanical service life | approx. 107cycles |
| Service life, electrical | see diagram |
| Mounting position | any |
| Net weight (SAP) | 82.9 g |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| Standards/regulations | IEC 60664 |
| IEC 61810 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 4 kV |
| Insulation | Basic insulation |
| Degree of pollution | 3 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |