View larger
PLT-SEC-T3-BE-FM-UT 2907924 PHOENIX CONTACT Type 3 surge protection base element
PLT-SEC-T3-BE-FM-UT
2907924
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact model PLT-SEC-T3-BE-FM-UT serves as a Type 3 surge protection base element designed for fine protection in automation and terminal equipment networks. This mounting base holds fine-protection modules and accommodates remote signaling contacts to integrate into broader industrial monitoring schemes. Specific pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2907924
- Packing unit: 10 pc
- GTIN: 4055626257709
- Weight per Piece (excluding packing): 48.000 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 93.4 mm
- Width: 17.7 mm
- Depth: 51.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
- Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
More info
▲Key Commercial Data
| Orderkey | 2907924 |
|---|---|
| Packing unit | 10 pc |
| GTIN | 4055626257709 |
| Weight per Piece (excluding packing) | 48.000 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| EN type | T2 / T3 |
|---|---|
| IEC power supply system | TN-S |
| TT | |
| Number of ports | One |
| Mounting type | DIN rail: 35 mm |
| Color | light gray RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Remote indication contact |
Protective circuit
| Nominal voltage UN | 240 V AC (TN-S) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| Rated load current IL | 26 A (at 30 °C) |
| Short-circuit current rating ISCCR | 10 kA AC |
| Max. backup fuse with branch wiring | depends on the plug used |
| Maximum backup fuse for through wiring | 25 A (gG / B / C) |
Additional technical data
| Short-circuit current rating ISCCR | max. 5 kA DC (depends on the plug used) |
|---|---|
| Maximum continuous voltage UC | 240 V DC |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 0.5 A AC |
| 0.5 A DC (75 V DC) | |
| Connection method | Screw connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 30 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 10 mm |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 10 mm |
UL specifications
| SPD Type | ACC |
|---|---|
| Nominal voltage | 240 V DC |
| Rated load current IL | 20 A |
| Power distribution system | Single phase |
| DC | |
| Nominal frequency | 50/60 Hz |
UL indicator/remote signaling
| Operating voltage | 250 V AC (0.5 A) |
|---|---|
| 12 V DC (4 A) | |
| 24 V DC (2 A) | |
| 48 V DC (1 A) | |
| Tightening torque | 5 lbf-in. ... 7 lbf-in. |
| Conductor cross section AWG | 30 ... 12 |