View larger
PLT-SEC-T3-BE-FM-PT 2907929 PHOENIX CONTACT Type 3 surge protection base element
PLT-SEC-T3-BE-FM-PT
2907929
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
PLT-SEC-T3-BE-FM-PT 2907929 PHOENIX CONTACT Type 3 surge protection base element units serve as the structural and electrical mounting foundation for fine protection plug modules in sensitive control circuits. Automation control panels employ these base elements to secure terminal wiring and integrate remote signaling contacts for comprehensive system monitoring. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 2907929 |
|---|---|
| Packing unit | 10 pc |
| GTIN | 4055626257679 |
| Weight per Piece (excluding packing) | 44.000 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| EN type | T2 / T3 |
|---|---|
| IEC power supply system | TN-S |
| TT | |
| Number of ports | One |
| Mounting type | DIN rail: 35 mm |
| Color | light gray RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Remote indication contact |
Protective circuit
| Nominal voltage UN | 240 V AC (TN-S) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| Rated load current IL | 26 A (at 30 °C) |
| Short-circuit current rating ISCCR | 10 kA AC |
| Max. backup fuse with branch wiring | depends on the plug used |
| Maximum backup fuse for through wiring | 25 A (gG / B / C) |
Additional technical data
| Short-circuit current rating ISCCR | max. 5 kA DC (depends on the plug used) |
|---|---|
| Maximum continuous voltage UC | 240 V DC |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 0.5 A AC |
| 0.5 A DC (75 V DC) | |
| Connection method | Push-in connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 30 ... 12 |
| Stripping length | 10 mm |
Connection data
| Connection method | Push-in connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Stripping length | 10 mm |