View larger
PLT-SEC-T3-24-P-UT/PT 2907920 PHOENIX CONTACT Type 3 surge protection plug
PLT-SEC-T3-24-P-UT/PT
2907920
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing precise voltage limitation, the PLT-SEC-T3-24-P-UT/PT 2907920 PHOENIX CONTACT Type 3 surge protection plug shields low-voltage electronic devices from transient electrical disturbances. These components are typically integrated at the end of power distribution paths inside automation enclosures to protect sensitive control gear. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2907920
- Packing unit: 10 pc
- GTIN: 4055626257464
- Weight per Piece (excluding packing): 35.170 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 46.7 mm
- Width: 17.5 mm
- Depth: 65.7 mm
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 6000 m (amsl (above mean sea level))
- Permissible humidity (operation): 5 % ... 95 %
- Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
More info
▲Key Commercial Data
| Orderkey | 2907920 |
|---|---|
| Packing unit | 10 pc |
| GTIN | 4055626257464 |
| Weight per Piece (excluding packing) | 35.170 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 6000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| EN type | T3 |
|---|---|
| IEC power supply system | TN-S |
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | on base element |
| Color | light gray RAL 7035 |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 2 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 24 V AC (TN-S) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 34 V AC |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs | 1 kA |
| Standby power consumption PC | ≤ 2.7 mVA (at UREF) |
| ≤ 4.8 mVA (at UC) | |
| Reference test voltage UREF | 27 V AC |
| Combination wave UOC | 2 kV |
| Voltage protection level Up(L-N) | ≤ 0.2 kV |
| Voltage protection level Up(L-PE) | ≤ 0.6 kV |
| Voltage protection level Up(N-PE) | ≤ 0.6 kV |
| TOV behavior at UT(L-N) | 50 V AC (120 min / safe failure mode) |
| TOV behavior at UT(L-PE) | 50 V AC (120 min / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Short-circuit current rating ISCCR | 10 kA AC |
| Max. backup fuse with branch wiring | 32 A (gG / B / C) |
Additional technical data
| Short-circuit current rating ISCCR | 0.25 kA DC (without additional backup fuse) |
|---|---|
| 5 kA DC (for 20 A gG / B backup fuse) | |
| Maximum discharge current Imax(8/20) µs | 4 kA |
| Nominal discharge current In(8/20) µs | 3 kA |
| Maximum continuous voltage UC | 44 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV | 34 V AC |
| 34 V DC | |
| Nominal voltage | 34 V DC |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| (DC+) - (DC-) | |
| (DC+) - G | |
| (DC-) - G | |
| Power distribution system | Single phase |
| DC | |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 200 V |
| Measured limiting voltage MLV (L-G) | 510 V |
| Measured limiting voltage MLV (N-G) | 510 V |
| Nominal discharge current In | 1 kA |