View larger
PLT-SEC-T3-24-FM-PT 2907925 PHOENIX CONTACT Type 3 surge protection device
PLT-SEC-T3-24-FM-PT
2907925
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for terminal equipment
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact part number PLT-SEC-T3-24-FM-PT (model PLT-SEC-T3-24-FM-PT 2907925 PHOENIX CONTACT Type 3 surge protection device) operates as a Type 3 surge protection device, designed to protect sensitive terminal loads from damaging voltage fluctuations. Such protective devices are standard in modern industrial distribution architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 34 V
- Voltage protection level L-N (EF004236): 0.2 kV
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 3 (EF004231): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2907925 |
|---|---|
| Packing unit | 5 pc |
| GTIN | 4055626257495 |
| Weight per Piece (excluding packing) | 77.160 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (operating voltage remote contact ≤ 250 V) |
| ≤ 6000 m (operating voltage remote contact ≤ 150 V) | |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| EN type | T3 |
|---|---|
| IEC power supply system | TN-S |
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light gray RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 24 V AC (TN-S) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 34 V AC |
| Rated load current IL | 26 A (at 30 °C) |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs | 1 kA |
| Standby power consumption PC | ≤ 2.7 mVA (at UREF) |
| ≤ 4.8 mVA (at UC) | |
| Reference test voltage UREF | 27 V AC |
| Combination wave UOC | 2 kV |
| Voltage protection level Up(L-N) | ≤ 0.2 kV |
| Voltage protection level Up(L-PE) | ≤ 0.6 kV |
| Voltage protection level Up(N-PE) | ≤ 0.6 kV |
| TOV behavior at UT(L-N) | 50 V AC (120 min / withstand mode) |
| TOV behavior at UT(L-PE) | 50 V AC (120 min / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Short-circuit current rating ISCCR | 10 kA AC |
| Max. backup fuse with branch wiring | 32 A (gG / B / C) |
| Maximum backup fuse for through wiring | 25 A (gG / B / C) |
Additional technical data
| Short-circuit current rating ISCCR | 0.25 kA DC (without additional backup fuse) |
|---|---|
| 5 kA DC (for 20 A gG / B backup fuse) | |
| Maximum discharge current Imax(8/20) µs | 4 kA |
| Nominal discharge current In(8/20) µs | 3 kA |
| Maximum continuous voltage UC | 44 V DC |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 0.5 A AC |
| 0.5 A DC (75 V DC) | |
| Connection method | Push-in connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 30 ... 12 |
| Stripping length | 10 mm |
Connection data
| Connection method | Push-in connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Stripping length | 10 mm |