Phoenix Contact part number PLT-SEC-T3-230-FM-UT (model PLT-SEC-T3-230-FM-UT 2907919 PHOENIX CONTACT Type 3 surge protection device) operates as a Type 3 surge protection device, designed to offer fine protection for terminal equipment against overvoltage spikes in electrical installations. Such devices are commonly deployed directly upstream of protected loads.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 264 V
- Voltage protection level L-N (EF004236): 1.25 kV
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- With remote signalling contact (EF000422): Yes
- Signalling at the device (EF004241): Optic
- Category type 3 (EF004231): No
- Degree of protection (IP) (EF005474): IP20
More info
▲Key Commercial Data
| Orderkey | 2907919 |
|---|---|
| Packing unit | 5 pc |
| GTIN | 4055626257457 |
| Weight per Piece (excluding packing) | 81.160 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (operating voltage remote contact ≤ 250 V) |
| ≤ 6000 m (operating voltage remote contact ≤ 150 V) | |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| EN type | T2 / T3 |
|---|---|
| IEC power supply system | TT |
| TN-S | |
| Number of ports | One |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | light gray RAL 7035 |
| traffic grey A RAL 7042 | |
| Housing material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 240 V AC (TN-S) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| Rated load current IL | 26 A (at 30 °C) |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs | 5 kA |
| Standby power consumption PC | ≤ 26.4 mVA (at UREF) |
| ≤ 26.4 mVA (at UC) | |
| Reference test voltage UREF | 264 V AC |
| Max. discharge current Imax(8/20) µs | 10 kA |
| Combination wave UOC | 6 kV |
| Voltage protection level Up(L-N) | ≤ 1.25 kV (at UOC) |
| ≤ 1.4 kV (at In) | |
| Voltage protection level Up(L-PE) | ≤ 1.4 kV |
| Voltage protection level Up(N-PE) | ≤ 1.4 kV |
| TOV behavior at UT(L-N) | 400 V AC (5 s / withstand mode) |
| 457 V AC (120 min / safe failure mode) | |
| TOV behavior at UT(L-PE) | 457 V AC (5 s / withstand mode) |
| 457 V AC (120 min / withstand mode) | |
| 1464 V AC (200 ms / safe failure mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Short-circuit current rating ISCCR | 10 kA AC |
| Max. backup fuse with branch wiring | 32 A (gG / B / C) |
| Maximum backup fuse for through wiring | 25 A (gG / B / C) |
Additional technical data
| Short-circuit current rating ISCCR | 0.25 kA DC (without additional backup fuse) |
|---|---|
| 5 kA DC (for 20 A gG / B backup fuse) | |
| Maximum continuous voltage UC | 240 V DC |
| IEC test classification (in accordance with IEC 61643-21) | D1 |
| Mode of protection | (DC+) - (DC-) |
| (DC+/DC-) - PE | |
| Impulse durability (line-line) | D1 - 500 A |
| Impulse durability (line-earth) | D1 - 500 A |
| Pulse discharge current Iimp(10/350) µs (line-line) | 0.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 250 V AC |
| 125 V DC (200 mA DC) | |
| Operating current | 0.5 A AC |
| 0.5 A DC (75 V DC) | |
| Connection method | Screw connection |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 30 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 10 mm |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 10 mm |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV | 264 V AC |
| 240 V DC | |
| Nominal voltage | 240 V DC |
| Rated load current IL | 20 A |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| (DC+) - (DC-) | |
| (DC+) - G | |
| (DC-) - G | |
| Power distribution system | Single phase |
| DC | |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 1150 V |
| Measured limiting voltage MLV (L-G) | 1180 V |
| Measured limiting voltage MLV (N-G) | 1180 V |
| Nominal discharge current In | 5 kA |
UL indicator/remote signaling
| Operating voltage | 250 V AC (0.5 A) |
|---|---|
| 12 V DC (4 A) | |
| 24 V DC (2 A) | |
| 48 V DC (1 A) | |
| Tightening torque | 5 lbf-in. ... 7 lbf-in. |
| Conductor cross section AWG | 30 ... 12 |