PHOENIX CONTACT PLT-SEC-T3-230-FM-PT PLT-SEC-T3-230-FM-PT 2907928 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLT-SEC-T3-230-FM-PT 2907928 PHOENIX CONTACT Type 3 surge protection device

PLT-SEC-T3-230-FM-PT

2907928

PHOENIX CONTACT

1 Pcs.

Type 3 surge protection device Type 2/3 surge protection, consisting of a plug-in protection and a base element with push-in connection. For single-phase power supply networks with integrated status indication and remote signal. Rated Voltage: 230VAC/DC

Automation > Surge protection device for terminal equipment
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact PLT-SEC-T3-230-FM-PT is a compact surge protection device designed to mount inside industrial control panels on standard DIN rails. Such fine-protection elements act as a final barrier in multi-stage suppression systems, stabilizing supply voltages for delicate electronic hardware.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Max. continuous voltage AC (EF004198): 264 V
  • Voltage protection level L-N (EF004236): 1.25 kV
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • With remote signalling contact (EF000422): Yes
  • Signalling at the device (EF004241): Optic
  • Category type 3 (EF004231): No
  • Degree of protection (IP) (EF005474): IP20

More info

▲

Key Commercial Data

Orderkey2907928
Packing unit5 pc
GTIN4055626257655
Weight per Piece (excluding packing)77.160 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height101 mm
Width17.7 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (operating voltage remote contact ≤ 250 V)
≤ 6000 m (operating voltage remote contact ≤ 150 V)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 ... 500 Hz / 2.5 h / X, Y, Z)

General

EN typeT2 / T3
IEC power supply systemTN-S
TT
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorlight gray RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL26 A (at 30 °C)
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs5 kA
Standby power consumption PC≤ 26.4 mVA (at UREF)
≤ 26.4 mVA (at UC)
Reference test voltage UREF264 V AC
Max. discharge current Imax(8/20) µs10 kA
Combination wave UOC6 kV
Voltage protection level Up(L-N)≤ 1.25 kV (at UOC)
≤ 1.4 kV (at In)
Voltage protection level Up(L-PE)≤ 1.4 kV
Voltage protection level Up(N-PE)≤ 1.4 kV
TOV behavior at UT(L-N)400 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
1464 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Short-circuit current rating ISCCR10 kA AC
Max. backup fuse with branch wiring32 A (gG / B / C)
Maximum backup fuse for through wiring25 A (gG / B / C)

Additional technical data

Short-circuit current rating ISCCR0.25 kA DC (without additional backup fuse)
5 kA DC (for 20 A gG / B backup fuse)
Maximum continuous voltage UC240 V DC
IEC test classification (in accordance with IEC 61643-21)D1
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Impulse durability (line-line)D1 - 500 A
Impulse durability (line-earth)D1 - 500 A
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA

Indicator/remote signaling

Switching functionPDT contact
Operating voltage250 V AC
125 V DC (200 mA DC)
Operating current0.5 A AC
0.5 A DC (75 V DC)
Connection methodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section AWG30 ... 12
Stripping length10 mm

Connection data

Connection methodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Stripping length10 mm

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.