Request QuoteProduct Overview
Phoenix Contact model PLC-OPT-230UC/ 48DC/100/SEN is a solid-state relay module designed for interfacing control signals with input functions. Relay interfaces of this nature provide galvanic isolation between field sensors and controller inputs, protecting sensitive logic components from voltage spikes and noise in industrial environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 184 V
- Type of voltage (input voltage) (EF003033): AC
- Output voltage (EF003933): 3 V
- Type of output voltage (EF008222): DC
- Rated operation current Ie (EF001443): 0.1 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Dimensions
| Width | 6.2 mm |
|---|---|
| Height | 80 mm |
| Depth | 94 mm |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Nominal input voltage UN | 230 V AC (220 V DC) |
|---|---|
| 220 V DC | |
| Input voltage range in reference to UN | 0.8 ... 1.1 |
| Switching threshold "0" signal in reference to UN | ≤ 0.3 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
| Typical input current at UN | 3.5 mA |
| Typical response time | 3 ms (at UN) |
| Typical turn-off time | 5 ms (at UN) |
| Operating voltage display | Yellow LED |
| Type of protection | Bridge rectifier |
| Protective circuit/component | Bridge rectifier |
| Transmission frequency | 10 Hz |
Output data
| Output voltage range | 3 V DC ... 48 V DC |
|---|---|
| Limiting continuous current | 100 mA |
| Voltage drop at max. limiting continuous current | ≤ 1 V |
| Output circuit | 2-wire, floating |
| Type of protection | Protection against polarity reversal |
| Surge protection | |
| Protective circuit/component | Polarity protection diode |
Connection data, input side
| Connection name | Input side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
General
| Test voltage input/output | 2.5 kV (50 Hz, 1 min.) |
|---|---|
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Flammability rating according to UL 94 | V0 |
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| IEC 62103 | |
| Rated surge voltage/insulation | Basic insulation |
| Pollution degree | 2 |
| Overvoltage category | III |