PLC-RPT- 24DC/21-21AU/MS 2910524 PHOENIX CONTACT Relay Module
PLC-RPT-24DC/21-21AU/MS
2910524
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact PLC-RPT-24DC/21-21AU/MS relay module provides interposing signal switching and electrical isolation between automation controllers and field peripheral devices. It is commonly deployed in control cabinets to match voltage levels, protect sensitive logic components, and safely switch moderate electrical loads.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 20.2 V
- Voltage type for actuating (EF008242): DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Gold
- Nominal current (EF000001): 0.018 A
- Degree of protection (IP) (EF005474): IP20
- Width (EF000008): 14 mm
More info
▲Key Commercial Data
| Orderkey | 2910524 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626486765 |
| Weight per Piece (excluding packing) | 64.000 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 24 V DC |
|---|---|
| Typical input current at UN | 18 mA |
| Typical response time | 10 ms |
| Typical release time | 10 ms |
| Coil voltage | 24 V DC |
| Protective circuit | Free-wheeling diode Damping diode |
| Operating voltage display | Yellow LED |
Contact side
| Contact type | 2 PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi + Au |
| Maximum switching voltage | 30 V AC |
| 36 V DC | |
| Minimum switching voltage | 12 V (1 mA) |
| Min. switching current | 1 mA (12 V) |
| Maximum inrush current | 50 mA |
| Limiting continuous current | 50 mA |
Contact side (with destroyed gold layer)
| Note | the following values are applicable if a gold layer is destroyed |
|---|---|
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 12 V |
| Limiting continuous current | 6 A |
| Maximum inrush current | 12 A (20 ms) |
| Min. switching current | 10 mA |
| Interrupting rating (ohmic load) max. | 192 W (24 V DC) |
| 62 W (48 V DC) | |
| 42 W (60 V DC) | |
| 55 W (110 V DC) | |
| 66 W (220 V DC) | |
| 2000 VA (250 V AC) | |
| Switching capacity | 1 A (24 V, DC13) |
| 1.5 A (230 V, AC15) |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
General
| Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
|---|---|
| Test voltage PDT/PDT | 2.5 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT II (Relay) |
| IP20 (Relay base) | |
| Mechanical service life | 5x 106cycles |
| UL, USA | UL 508 |
| UL 508 Recognized | |
| UL, USA/Canada | cUL 508 |
| cUL 508 Recognized | |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | EN 50178 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
| UL, USA | UL 508 |
| UL 508 Recognized | |
| UL, USA/Canada | cUL 508 |
| cUL 508 Recognized |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |