The PLC-RPT-230UC/21HC/EX 2909534 PHOENIX CONTACT Relay Module is an industrial interface component designed for signal conditioning, electrical isolation, and amplification between control hardware and field devices in automation panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 179.4 V
- Rated control supply voltage AC 60 Hz (EF003979): 179.4 V
- Rated control supply voltage DC (EF003980): 171.6 V
- Voltage type for actuating (EF008242): AC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 1
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.0045 A
More info
▲Key Commercial Data
| Orderkey | 2909534 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 459 (C-5-2017) |
| GTIN | 4055626363714 |
| Weight per Piece (excluding packing) | 66.450 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (UL) |
|---|---|
| -40 °C ... 55 °C (ATEX / IECEx) | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 230 V AC |
|---|---|
| 220 V DC | |
| Typical input current at UN | 4.5 mA |
| Typical response time | 7 ms |
| Typical release time | 10 ms |
| Protective circuit | Bridge rectifier Bridge rectifier |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 1.04 W |
Contact side
| Contact type | 1 PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum switching voltage | 12 V (at 10 mA) |
| Min. switching current | 10 mA (at 12 V) |
| Maximum inrush current | 30 A (300 ms) |
| Limiting continuous current | 10 A |
| 6 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.) | |
| Interrupting rating (ohmic load) max. | 240 W (at 24 V DC) |
| 58 W (at 48 V DC) | |
| 48 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 80 W (at 220 V DC) | |
| 2500 VA (for 250 V AC) | |
| Interrupting rating (ohmic load) max. bridged | 144 W (for 24 V DC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) |
| 1500 VA (for 250 V AC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 0.2 A (at 110 V, DC13) | |
| 0.2 A (at 250 V, DC13) | |
| 6 A (at 24 V, AC15) | |
| 6 A (at 120 V, AC15) | |
| 6 A (at 250 V, AC15) |
General
| Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
|---|---|
| Operating mode | 100% operating factor |
| Degree of protection | RT II (Relay) |
| IP20 (Relay base) | |
| Mechanical service life | 3x 107cycles |
| ATEX | II 3G Ex ec nC IIC T4 Gc |
| EU-type examination certificate | IBExU16ATEXB015 X |
| IECEx | Ex ec nC IIC T4 Gc |
| IECEx certificate | IECEx IBE 16.0029X |
| UL, USA | Class I, Zone 2, AEx nA nC IIC T6 |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
| UL, Canada | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 66.45 g |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| EN 60079-0, -7, -15 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation, reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant |
| ATEX | II 3G Ex ec nC IIC T4 Gc |
| IECEx | Ex ec nC IIC T4 Gc |
| UL, USA | Class I, Zone 2, AEx nA nC IIC T6 |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
| UL, Canada | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |