View larger
PLC-RPT- 24DC/21-21 2900330 PHOENIX CONTACT Relay Module
PLC-RPT-24DC/21-21
2900330
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A terminal-style relay module bridges the gap between delicate controller outputs and high-power industrial actuators. Designed for DIN-rail mounting, this Phoenix Contact PLC-RPT-24DC/21-21 hardware isolates control circuits and switches loads efficiently within cramped control cabinets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 20.2 V
- Voltage type for actuating (EF008242): DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 2
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.018 A
- Degree of protection (IP) (EF005474): IP20
- Width (EF000008): 14 mm
More info
▲Key Commercial Data
| Orderkey | 2900330 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 374 (C-5-2017) |
| GTIN | 4046356509893 |
| Weight per Piece (excluding packing) | 58.100 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Coil side
| Nominal input voltage UN | 24 V DC |
|---|---|
| Typical input current at UN | 18 mA |
| Typical response time | 8 ms |
| Typical release time | 10 ms |
| Protective circuit | Reverse polarity protection Polarity protection diode |
| Free-wheeling diode Damping diode | |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.43 W |
Contact side
| Contact type | 2 PDT |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum switching voltage | 5 V AC/DC (at 10 mA) |
| Min. switching current | 10 mA (At 5 V) |
| Maximum inrush current | 15 A (300 ms) |
| Limiting continuous current | 6 A |
| Interrupting rating (ohmic load) max. | 140 W (at 24 V DC) |
| 85 W (at 48 V DC) | |
| 60 W (at 60 V DC) | |
| 44 W (at 110 V DC) | |
| 60 W (at 220 V DC) | |
| 1500 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) |
| 3 A (at 24 V, AC15) | |
| 3 A (at 120 V, AC15) | |
| 3 A (at 250 V, AC15) | |
| 0.2 A (at 250 V, DC13) |
Connection data 1
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
Connection data 2
| Connection name | Contact side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
General
| Operating mode | 100% operating factor |
|---|---|
| Degree of protection | RT III (Relay) |
| IP20 (Relay base) | |
| Mechanical service life | 3x 107cycles |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 58.1 g |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Designation | Standards/regulations |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation of input/output |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |