View larger
PLC-RPT- 24DC/ 1IC/ACT 2900298 PHOENIX CONTACT Relay Module
PLC-RPT-24DC/ 1IC/ACT
2900298
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A PLC-RPT- 24DC/ 1IC/ACT 2900298 PHOENIX CONTACT Relay Module from Phoenix Contact is utilized within industrial automation systems to provide efficient signal matching, switching, and galvanic isolation between controllers and actuators. Modular relay blocks optimize panel space and streamline wiring layouts.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 20.2 V
- Voltage type for actuating (EF008242): DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.018 A
- Degree of protection (IP) (EF005474): IP20
- Width (EF000008): 14 mm
More info
▲Key Commercial Data
| Orderkey | 2900298 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 386 (C-5-2017) |
| GTIN | 4046356507370 |
| Weight per Piece (excluding packing) | 56.800 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|---|
| Note | Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. |
| The PLC-ATP separating plate should be installed for safe isolation between adjacent modules | |
| The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. | |
| The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
| Width | 14 mm |
|---|---|
| Height | 80 mm |
| Depth | 94 mm |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
Coil side
| Nominal input voltage UN | 24 V DC |
|---|---|
| Typical input current at UN | 18 mA |
| Typical response time | 8 ms |
| Typical release time | 10 ms |
| Coil voltage | 24 V DC |
| Protective circuit | Reverse polarity protection Polarity protection diode |
| Free-wheeling diode Damping diode | |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.43 W |
Contact side
| Contact type | 1 N/O contact |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum switching voltage | 12 V (at 100 mA) |
| Min. switching current | 100 mA (at 12 V DC) |
| Maximum inrush current | 80 A (20 ms) |
| 130 A (peak, at capacitive load, 230 V AC, 24 μF) | |
| Limiting continuous current | 6 A |
| 10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged) | |
| Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
| 58 W (at 48 V DC) | |
| 48 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 80 W | |
| 85 W (for 250 V DC) | |
| 1500 VA (for 250 V AC) | |
| Interrupting rating (ohmic load) max. bridged | 240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) |
| 2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) | |
| Switching capacity min. | 1200 mW |
| Switching capacity | 2 A (at 24 V, DC13) |
| 0.2 A (at 110 V, DC13) | |
| 0.2 A (at 250 V, DC13) | |
| 6 A (at 24 V, AC15) | |
| 6 A (at 120 V, AC15) | |
| 6 A (at 250 V, AC15) |
| Connection name | Coil side |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
| Connection name | Contact side |
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² () | |
| 2x 0.5 mm² ... 1 mm² () | |
| Conductor cross section AWG | 26 ... 14 |
General
| Note | Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. |
|---|---|
| The PLC-ATP separating plate should be installed for safe isolation between adjacent modules | |
| The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. | |
| The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. | |
| Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Degree of protection | RT II (Relay) |
| IP20 (Relay base) | |
| Mechanical service life | 3x 107cycles |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 56.8 g |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Designation | Standards/regulations |
| Standards/regulations | EN 50178 |
| EN 61810-1 | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage | 6 kV |
| Insulation | Safe isolation, reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |