PHOENIX CONTACT PLC-RPT-230UC/21HC PLC-RPT-230UC/21HC 2900297 PHOENIX CONTACT Relay Module View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLC-RPT-230UC/21HC 2900297 PHOENIX CONTACT Relay Module

PLC-RPT-230UC/21HC

2900297

PHOENIX CONTACT

10 Pcs.

Relay Module PLC-INTERFACE for high constant currents, consisting of PLC-BPT.../21 HC base terminal block with push-in connection and plug-in miniature relay, for mounting on NS 35/7.5 rail, constant current limit up to 10 A, 1 switched contact, input voltage 230 V AC/DC PLC-INTERFACE for high continuous currents, consisting of PLC-BPT.../21 HC basic terminal block with Push-in connection and plug-in miniature relay, for mounting on DIN rail NS 35/7,5, limiting continuous current up to 10 A, 1 changeover contact, input voltage 230 V AC/DC

Automation > Switching relay
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact PLC-RPT-230UC/21HC 2900297 PHOENIX CONTACT Relay Module provides dependable electrical isolation and signal switching for heavy-duty industrial environments. Such relay modules are routinely deployed in manufacturing plants to interface PLC logic outputs with high-capacity actuators, valves, and motor starters. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Relay Module
  • Product family: PLC-INTERFACE
  • Application: High continuous currents
  • Operating mode: 100% operating factor
  • Mechanical service life: 3x 10 7 cycles
  • Data management status Date of last data management: 11.07.2024
  • Article revision: 09
  • Insulation characteristics Insulation: Safe isolation, reinforced insulation
  • Overvoltage category: III
  • Pollution degree: 3
  • Maximum power dissipation for nominal condition: 0.99 W
  • Rated surge voltage: 6 kV
  • Coil side Nominal input voltage U N: 230 V AC
  • Input voltage range: 179.4 V AC ... 264.5 V AC (20 °C)
  • Nominal voltage (plugged-in electromechanical relay): 110 V DC
  • Drive and function: monostable

More info

▲
Technical data

Product properties
Product typeRelay Module
Product familyPLC-INTERFACE
ApplicationHigh continuous currents
Operating mode100% operating factor
Mechanical service life3x 107cycles
Data management status
Date of last data management11.07.2024
Article revision09
Insulation characteristics
InsulationSafe isolation, reinforced insulation
Overvoltage categoryIII
Pollution degree3

Electrical properties
Maximum power dissipation for nominal condition0.99 W
Rated surge voltage6 kV

Input data
Coil side
Nominal input voltage UN230 V AC
220 V DC
Input voltage range179.4 V AC ... 264.5 V AC (20 °C)
171.6 V DC ... 264 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)110 V DC
Drive and functionmonostable
Drive (polarity)polarized
Typical input current at UN4.3 mA (at 220 V DC)
4.5 mA (at 230 V AC)
Typical response time7 ms
Typical release time10 ms
Protective circuitBridge rectifier; Bridge rectifier
Operating voltage displayYellow LED

Output data
Switching
Contact switching type1 changeover contact
Type of switch contactSingle contact
Contact materialAgNi
Maximum switching voltage250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage12 V (10 mA)
Limiting continuous current10 A
6 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.)
Maximum inrush current30 A (300 ms)
Min. switching current10 mA (12 V)
Interrupting rating (ohmic load) max.240 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
2500 VA (for 250 V AC)
Interrupting rating (ohmic load) max. bridged144 W (for 24 V DC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.)
1500 VA (for 250 V AC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.)
Switching capacity2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
6 A (at 24 V, AC15)
6 A (at 120 V, AC15)
6 A (at 250 V, AC15)

Connection data
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG26 ... 14

Dimensions
Width14 mm
Height80 mm
Depth94 mm

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)

Environmental and real-life conditions
Ambient conditions
Degree of protection (Relay)RT II (Relay)
Degree of protection (Relay base)IP20 (Relay base)
Ambient temperature (operation)-40 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Approvals
CE
CertificateCE-compliant
UKCA
CertificateUKCA-compliant
Shipbuilding approval
CertificateTAE0000196
Corrosive gas test
IdentificationISA-S71.04. G3 Harsh Group
EN 60068-2-60
DNV GL data
TemperatureD
HumidityA
VibrationB/C
EMCB
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data
Electromagnetic compatibilityConformance with EMC directive
Low Voltage DirectiveConformance with Low Voltage Directive

Standards and regulations
Standards/regulationsIEC 60947-5-1

Mounting
Mounting typeDIN rail mounting
Assembly notein rows with zero spacing
Mounting positionany

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.