PHOENIX CONTACT PLC-OPT-120UC/230AC/1 PLC-OPT-120UC/230AC/1 2900372 PHOENIX CONTACT PLC-INTERFACE, consisting of PLC-BPT.../21 basic terminal bloc.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLC-OPT-120UC/230AC/1 2900372 PHOENIX CONTACT PLC-INTERFACE, consisting of PLC-BPT.../21 basic terminal bloc..

PLC-OPT-120UC/230AC/1

2900372

PHOENIX CONTACT

1 Pcs.

PLC-INTERFACE, consisting of PLC-BPT.../21 basic terminal block with push-in connection and plug-in miniature solid-state relay, for mounting on DIN rail NS 35/7,5, 1 N/O contact, input: 120 V AC/110 V DC, output: 24 - 253 V AC/0.75 A

Automation > Optocoupler
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact PLC-OPT-120UC/230AC/1 is a PLC-INTERFACE terminal block designed for galvanic isolation and signal matching between control systems and field devices. Solid-state relay interfaces provide wear-free, rapid switching of electrical loads in industrial automation panels.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Input voltage (EF003840): 108 V
  • Type of voltage (input voltage) (EF003033): AC
  • Output voltage (EF003933): 24 V
  • Type of output voltage (EF008222): AC
  • Rated operation current Ie (EF001443): 0.75 A
  • Type of digital output (EF003601): Electronic
  • With LED indication (EF005950): Yes

More info

▲

Dimensions

Width6.2 mm
Height80 mm
Depth94 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C

Input data

Nominal input voltage UN120 V AC (110 V DC)
110 V DC
Input voltage range in reference to UN0.9 ... 1.1
Switching threshold "0" signal in reference to UN≤ 0.25
Switching threshold "1" signal in reference to UN≥ 0.8
Typical input current at UN4 mA
Typical response time10 ms (at UN)
Typical turn-off time10 ms (at UN)
Operating voltage displayYellow LED
Type of protectionBridge rectifier
Protective circuit/componentBridge rectifier
Transmission frequency3 Hz

Output data

Output voltage range24 V AC ... 253 V AC
Limiting continuous current0.75 A (see derating curve)
Maximum inrush current30 A (10 ms)
Min. load current10 mA
Leakage current< 1 mA (in off state)
Max. load value4.5 A2s
Voltage drop at max. limiting continuous current< 1 V
Output circuit2-wire, floating
Type of protectionRCV circuit

Connection data, input side

Connection nameInput side
Connection methodPush-in connection
Stripping length8 mm
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG26 ... 14

General

Test voltage input/output2.5 kV (50 Hz, 1 min.)
Mounting positionany
Assembly instructionsIn rows with zero spacing
Operating mode100% operating factor
Flammability rating according to UL 94V0
Pollution degree2
Overvoltage categoryIII

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.