View larger
PLC-OPT- 24DC/230AC/2.4/ACT 2904632 PHOENIX CONTACT Solid-state relay module
PLC-OPT-24DC/230AC/2.4/ACT
2904632
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact PLC-OPT- 24DC/230AC/2.4/ACT Solid-state relay module is engineered to manage output functions in industrial control systems by routing signals reliably between PLCs and higher voltage loads. These interface modules protect delicate control hardware from feedback surges while ensuring high-frequency switching performance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Solid-state relay module
- Product family: PLC-INTERFACE
- Application: Output function
- Operating mode: 100% operating factor
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: III
- Pollution degree: 2
- Maximum power dissipation for nominal condition: 0.19 W
- Test voltage (Input/output): 2.5 kV (50 Hz, 1 min., input/output)
- Rated surge voltage: 4 kV
- Rated actuating voltage U C: 24 V DC
- Voltage range with reference to U C: 0.8 ... 1.2
- Rated actuating current I C: 8 mA
- Input voltage range: 19.2 V DC ... 28.8 V DC
- "0" signal switching threshold in reference to U C: < 0.4
- "1" signal switching threshold in reference to U C: > 0.8
More info
▲| Product type | Solid-state relay module |
| Product family | PLC-INTERFACE |
| Application | Output function |
| Operating mode | 100% operating factor |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Insulation characteristics: Air clearances and creepage distances between the power circuits | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | 0.19 W |
| Test voltage (Input/output) | 2.5 kV (50 Hz, 1 min., input/output) |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 260 V AC |
| Rated surge voltage | 4 kV |
| Rated actuating voltage UC | 24 V DC |
| Voltage range with reference to UC | 0.8 ... 1.2 |
| Rated actuating current IC | 8 mA |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| "0" signal switching threshold in reference to UC | < 0.4 |
| "1" signal switching threshold in reference to UC | > 0.8 |
| Typical response time | 10 ms (at UC) |
| Typical turn-off time | 10 ms (at UC) |
| Status display | Yellow LED |
| Protective circuit | Reverse polarity protection |
| Surge protection | |
| Surge voltage protection | > 33 V |
| Transmission frequency | 10 Hz |
| Designation | Output data |
| Contact switching type | 1 N/O contact |
| Design of digital output | electronic |
| Contact connection type | Power contact |
| Output voltage range | 24 V AC ... 253 V AC |
| Limiting continuous current | 2.4 A (see to derating) |
| Maximum inrush current | 250 A (20 ms) |
| Min. load current | 10 mA |
| Leakage current | < 3 mA |
| Max. load value | 340 A2s (tp = 10 ms, at 25 °C) |
| Surge voltage protection | > 275 V |
| Voltage drop at max. limiting continuous current | < 1 V |
| Output circuit | 2-conductor, zero voltage switch |
| Protective circuit | RCV circuit |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² (Single ferrule) | |
| 2x 0.5 mm² ... 1 mm² (TWIN ferrule) | |
| Conductor cross section AWG | 26 ... 14 |
| Width | 6.2 mm |
| Height | 80 mm |
| Depth | 95 mm |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | IEC 60947-5-1 |
| Mounting type | DIN rail mounting |
| Assembly instructions | in rows with zero spacing |
| Mounting position | any |