View larger
PLC-BPT-120UC/ 1/SEN 2900451 PHOENIX CONTACT Relay base
PLC-BPT-120UC/ 1/SEN
2900451
PHOENIX CONTACT
10 Pcs.
Automation > Relay socket
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The PLC-BPT-120UC/ 1/SEN 2900451 PHOENIX CONTACT Relay base is engineered to support industrial interface modules and input sensor circuits within automated control panels. Socket bases streamline cabinet architecture by terminating control wiring securely while isolating input channels from system controllers.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Relay socket
- Product family: PLC-INTERFACE
- Application: Input function
- Data management status Article revision: 05
- Nominal input voltage U N: 120 V AC/DC
- Protective circuit: Bridge rectifier
- Nominal input voltage U N: 120 V AC/DC
- Connection method: Push-in connection
- Stripping length: 10 mm
- Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
- Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
- Conductor cross section AWG: 26 ... 14
- Width: 6.2 mm
- Height: 80 mm
- Depth: 94 mm
More info
▲| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Relay socket |
| Product family | PLC-INTERFACE |
| Application | Input function |
| Data management status | |
| Article revision | 05 |
| Nominal input voltage UN | 120 V AC/DC |
| The nominal voltage of the plug-on electromechanical relay or solid-state relay (see necessary accessories) deviates from the nominal input voltage of the base with integrated upstream circuit | |
| Protective circuit | Bridge rectifier |
| Nominal input voltage UN | 120 V AC/DC |
| The nominal voltage of the plug-on electromechanical relay or solid-state relay (see necessary accessories) deviates from the nominal input voltage of the base with integrated upstream circuit |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| 0.2 mm² ... 2.5 mm² (Single ferrule) | |
| 2x 0.5 mm² ... 1 mm² (TWIN ferrule) | |
| Conductor cross section AWG | 26 ... 14 |
| Width | 6.2 mm |
| Height | 80 mm |
| Depth | 94 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -40 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| CE | |
| Certificate | CE-compliant |
| UKCA | |
| Certificate | UKCA-compliant |
| Shipbuilding approval | |
| Certificate | TAE0000196 |
| Corrosive gas test | |
| Identification | ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 | |
| DNV GL data | |
| Temperature | D |
| Humidity | A |
| Vibration | B/C |
| EMC | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Mounting type | DIN rail mounting |
| Mounting position | any |