AGK 10-UKH 50 3001763 PHOENIX CONTACT Pick-off terminal block
AGK 10-UKH 50
3001763
PHOENIX CONTACT
10 Pcs.
Connectors > Terminal block connector
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
AGK 10-UKH 50 3001763 PHOENIX CONTACT Pick-off terminal block components facilitate secure auxiliary circuit connections alongside main power distribution terminals in industrial switchgear. Engineers use these modular accessories to distribute control signals or tap power safely within high-capacity electrical panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.5 mm²
- Connectable conductor cross section multi-wired (EF007343): 0.5 mm²
- Rated current In (EF008250): 57 A
- Rated voltage (EF000228): 1000 V
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of clamp positions per level (EF002660): 1
- Suitable for conductor material (EF012572): Aluminium/copper
- Width (EF000008): 11.5 mm
- Height (EF000040): 46.5 mm
- Depth (EF000049): 34.7 mm
- Explosion-tested version 'Ex e' (EF008498): Yes
- Closing plate required (EF002525): No
- Colour (EF000007): Grey
- Internally connected stages (EF002661): Yes
More info
▲Key Commercial Data
| Orderkey | 3001763 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Catalog page | Page 256 (C-1-2017) |
| GTIN | 4017918100865 |
| Weight per Piece (excluding packing) | 14.680 g |
| Custom tariff number | 85369010 |
| Country of origin | PL (Poland) |
General
| Color | gray |
|---|---|
| Insulating material | PA |
| Nominal cross section | 10 mm² |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.82 W |
| Connection in acc. with standard | IEC/EN 60079-7 |
| Nominal current IN | 57 A |
| Maximum load current | 57 A (with 10 mm² conductor cross section) |
| Nominal voltage UN | 1000 V |
| Open side panel | No |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Conductor cross section solid min. | 0.5 mm² |
|---|---|
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 8 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 10 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 6 mm² |
| 2 conductors with same cross section, solid min. | 0.5 mm² |
| 2 conductors with same cross section, solid max. | 4 mm² |
| 2 conductors with same cross section, stranded min. | 0.5 mm² |
| 2 conductors with same cross section, stranded max. | 4 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 2.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 6 mm² |
| Connection method | Screw connection |
| Stripping length | 10 mm |
| Internal cylindrical gage | B6 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC/EN 60079-7 | |
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |