View larger
QUINT-UPS/ 24DC/ 24DC/10/3.4AH 2320267 PHOENIX CONTACT Uninterruptible power supply
QUINT-UPS/ 24DC/ 24DC/10/3.4AH
2320267
PHOENIX CONTACT
1 Pcs.
Automation > UPS
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Maintaining continuous DC power during primary circuit interruptions, this Phoenix Contact uninterruptible power supply safeguards industrial controllers and field sensors. Backup modules integrate seamlessly into DIN rail mounting configurations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 18 V
- Output voltage (EF003933): 24 V
- SNMP (EF005284): No
- Voltage type (EF000187): DC
- Height (EF000040): 169 mm
- Width (EF000008): 120 mm
- Depth (EF000049): 125 mm
- Weight (EF000167): 4.114 kg
- Bridging time full load (EF000428): 600 min
More info
▲Key Commercial Data
| Orderkey | 2320267 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 294 (C-4-2017) |
| GTIN | 4046356554183 |
| Weight per Piece (excluding packing) | 4,434.000 g |
| Custom tariff number | 85371091 |
| Country of origin | CN (China) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | 0 °C ... 40 °C |
| Ambient temperature (storage/transport) | -15 °C ... 40 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
Input data
| Input voltage | 24 V DC |
|---|---|
| Input voltage range | 18 V DC ... 30 V DC |
| Current consumption (maximum) | 18.6 A (24 V DC) |
| Current consumption (idle) | 9.5 mA |
| Current consumption (charging process) | 3.6 A |
Output data (24 V DC mains operation)
| Nominal output voltage | 24 V DC |
|---|---|
| Output voltage range (depends on the input voltage) | 18 V DC ... 30 V DC |
| Nominal output current (IN) | 10 A (0 °C ... 40 °C) |
| POWER BOOST (IBoost) | 15 A (0 °C ... 40 °C) |
| Selective Fuse Breaking (ISFB) | 60 A (0 °C ... 40 °C) |
Output data (24 V DC battery operation)
| Nominal output voltage | 24 V DC |
|---|---|
| Output voltage range (depends on the input voltage) | 19.2 V DC ... 27.6 V DC (UOUT= UBAT- 0.5 V DC) |
| Nominal output current (IN) | 10 A (0 °C ... 40 °C) |
| POWER BOOST (IBoost) | 15 A (0 °C ... 40 °C) |
| Selective Fuse Breaking (ISFB) | 65 A (0 °C ... 40 °C) |
General
| IQ technology | Yes |
|---|---|
| Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer. |
| Net weight | 3.8 kg |
| Memory medium | Lead rechargeable battery module, 3.4 Ah |
| Protection class | III |
| MTBF (IEC 61709, SN 29500) | > 806000 h (40 °C) |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: horizontal 5 mm, vertical 50 mm |
Connection data, input
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Pluggable screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M4 |
Connection data for signaling
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M4 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Criterion A) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| EN 61558-2-17 | |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| UL approvals | UL/C-UL Recognized UL 60950-1 |
| UL Listed UL 508 | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g tv= 90 min. | |
| Rail applications | EN 50121-4 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 3 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |