PHOENIX CONTACT IB IL 24 DO 16-PAC/SN IB IL 24 DO 16-PAC/SN 2862961 PHOENIX CONTACT Inline terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IB IL 24 DO 16-PAC/SN 2862961 PHOENIX CONTACT Inline terminal

IB IL 24 DO 16-PAC/SN

2862961

PHOENIX CONTACT

1 Pcs.

Inline terminal Inline, Digital output module, Digital outputs:16, 24 VDC, 500 mA, connection technology:3 conductors, transmission speed on the local bus:500 kBit/s, protection index: IP20, including inline connectors and marking fields, individually numbered connectors Inline, Digital output terminal, Digital outputs: 16, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields, connectors numbered individually

Automation > Fieldbus, decentr. periphery - digital I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact IB IL 24 DO 16-PAC/SN inline terminal functions as a modular I/O device within distributed control systems, allowing controllers to communicate reliably with field-level actuators and indicators. Inline terminals help organize complex wiring layouts inside electrical enclosures while maintaining high-speed data transmission. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Width: 48.8 mm
  • Height: 140.5 mm
  • Depth: 71.5 mm
  • Note on dimensions: Housing dimensions
  • Note on application Note on application: Only for industrial use
  • Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China.
  • Inline local bus Number of interfaces: 2
  • Connection method: Inline data jumper
  • Transmission speed: 500 kbps
  • Module ID code (dec.): 189
  • ID code (hex): BD
  • Length code (hex): 01
  • Length code (dec): 01
  • Process data channel: 16 bit
  • Input address area: 0 Byte
  • Output address area: 2 Byte

More info

▲
Technical data

Dimensions
Dimensional drawing
Width48.8 mm
Height140.5 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Notes
Note on application
Note on applicationOnly for industrial use
Utilization restriction
CCCex noteUse in potentially explosive areas is not permitted in China.

Interfaces
Inline local bus
Number of interfaces2
Connection methodInline data jumper
Transmission speed500 kbps

System properties
Module
ID code (dec.)189
ID code (hex)BD
Length code (hex)01
Length code (dec)01
Process data channel16 bit
Input address area0 Byte
Output address area2 Byte
Register length16 bit
Required parameter data4 Byte
Required configuration data4 Byte

Output data
Digital:
Output nameDigital outputs
Connection methodSpring-cage connection
Connection technology3-conductor
Number of outputs16
Protective circuitOverload protection, short-circuit protection of outputs; electronic
Output voltage24 V DC (US- 1 V)
Limitation of the voltage induced on circuit interruption-46 V ... -15 V
Maximum inrush currentmax. 1.5 A (at nominal lamp load for 20 ms)
Output currentmax. 500 mA (per channel)
max. 8 A (Device)
Nominal output voltage24 V DC
Output voltage when switched offmax. 2 V
Output current when switched offmax. 300 µA
Nominal load, inductive12 W (1.2 H, 48 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 VA (48 Ω)
Maximum operating frequency with ohmic nominal loadmax. 300 Hz (this switching frequency is limited by the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulsesReverse voltage proof
Behavior with overloadAuto restart
Behavior with inductive overloadOutput can be destroyed
Behavior at voltage switch-offThe output follows the power supply without delay
Overcurrent shut-downmin. 0.7 A
Output current with ground connection interrupt when switched offmax. 25 mA

Product properties
Product typeI/O component
Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields, connectors numbered individually
No. of channels16
Operating modeProcess data mode with one word
Diagnostics messagesShort-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Data management status
Article revision11
Insulation characteristics
Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties
Maximum power dissipation for nominal condition3.4 W
Potentials: Communications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current drawmax. 90 mA
Potentials: Segment circuit supply (US)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic)/functional ground500 V AC, 50 Hz, 1 min.

Connection data
Connection technology
Connection nameInline connector
Conductor connection
Connection methodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm
Inline connector
Connection methodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-25 °C ... 55 °C
Degree of protectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and regulations
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting
Mounting typeDIN rail mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.