View larger
OTTA 6 YE 0790620 PHOENIX CONTACT Bolt connection terminal block
OTTA 6 YE
0790620
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact OTTA 6 YE is a bolt connection terminal block designed to facilitate secure and reliable electrical conductor terminations within industrial control panels and power distribution setups. Terminal blocks like this are commonly utilized to organize, distribute, and protect complex wiring systems in various machinery and automation infrastructure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 0790620
- Packing unit: 50 pc
- Note: Made to Order (non-returnable)
- GTIN: 4046356342988
- Weight per Piece (excluding packing): 22.930 g
- Custom tariff number: 85369010
- Country of origin: IN (India)
- Number of levels: 1
- Number of connections: 2
- Nominal cross section: 6 mm²
- Color: yellow
- Insulating material: PA
- Flammability rating according to UL 94: V0
- Rated surge voltage: 8 kV
- Degree of pollution: 3
- Overvoltage category: III
More info
▲Key Commercial Data
| Orderkey | 0790620 |
|---|---|
| Packing unit | 50 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4046356342988 |
| Weight per Piece (excluding packing) | 22.930 g |
| Custom tariff number | 85369010 |
| Country of origin | IN (India) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Nominal cross section | 6 mm² |
| Color | yellow |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.31 W |
| Connection in acc. with standard | IEC 60947-7-1 |
| Nominal current IN | 41 A |
| Maximum load current | 41 A (with 6 mm² conductor cross section) |
| Nominal voltage UN | 800 V (the nominal voltage applies to insulated cable lugs) |
| Open side panel | Yes |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32/NS 35 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 6 mm² |
| Short-time current | 0.72 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Dimensions
| Length | 43.5 mm |
|---|---|
| Width | 11 mm |
| Height NS 35/7,5 | 52 mm |
| Height NS 35/15 | 59.5 mm |
| Height NS 32 | 57 mm |
Connection data
| Connection method | Bolt connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.1 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.1 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 6 mm² |
| Cable lug connection according to standard | DIN 46234 |
| Min. cross section for cable lug connection | 0.1 mm² |
| Max. cross section for cable lug connection | 6 mm² |
| Hole diameter, min. | 4.3 mm |
| Cable lug width, max. | 9.6 mm |
| Bolt diameter | 4 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter, min. | 4.3 mm |
| Cable lug width, max. | 9.6 mm |
| Bolt diameter | 4 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |