PLC-APT-PT100-IN 2906919 PHOENIX CONTACT Extension module
PLC-APT-PT100-IN
2906919
PHOENIX CONTACT
1 Pcs.
Automation > PLC analogue I/O-module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PLC-APT-PT100-IN is an extension module configured to interface resistance thermometer sensors with control circuits for accurate temperature tracking. Signal extension and interface components ensure that industrial field devices communicate reliably with higher-level controllers. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of analogue inputs (EF001994): 1
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): Yes
- Analogue outputs configurable (EF008519): No
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): Yes
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Resolution of the analogue inputs (EF003575): 10 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
More info
▲Key Commercial Data
| Orderkey | 2906919 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 431 (C-5-2017) |
| GTIN | 4055626155500 |
| Weight per Piece (excluding packing) | 50.300 g |
| Custom tariff number | 85389099 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Supply
| Rated control circuit supply voltage US | 24 V DC |
|---|---|
| Rated control supply voltage range with reference to US | 0.8 ... 1.1 |
| Rated control supply current IS | 14 mA |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Operating voltage display | Green LED |
| Indication | Red LED |
Input data
| Input name | Analog input resistance |
|---|---|
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751, α = 0,00385) |
| Connection technology | 2-wire |
| Sensor input current | ~ 900 µA |
| Maximum temperature coefficient | 0.01 %/K |
| Temperature measuring range | -50 °C ... 200 °C |
| Maximum transmission error | 1 % |
| Surge voltage protection | > 33 V |
| Input name | Analog input resistance |
| Sensor types (RTD) that can be used | Pt 1000 (IEC 60751, α = 0.00385) |
| Connection technology | 2-wire |
| Sensor input current | ~ 900 µA |
| Maximum temperature coefficient | 0.01 %/K |
| Temperature measuring range | -50 °C ... 200 °C |
| Maximum transmission error | 1 % |
| Surge voltage protection | > 33 V |
General
| Operating mode | 100% operating factor |
|---|---|
| Degree of protection | IP20 |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
| Number of connections | 4 |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 50 V |
| Rated surge voltage | 0.5 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Conformance | CE-compliant |
| UL, USA/Canada | UL 508 Listed |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |