PHOENIX CONTACT PT 6-TG PT 6-TG 3212163 PHOENIX CONTACT Disconnect terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT 6-TG 3212163 PHOENIX CONTACT Disconnect terminal block

PT 6-TG

3212163

PHOENIX CONTACT

50 Pcs.

Disconnect terminal block Interruptible terminal, Current and voltage are determined by the connector used., nominal voltage: 500 V, nominal current: 20 A, connection type: Push-in connection, Dimensioning section: 6 mm², section: 0.5 mm² - 10 mm², mounting: NS 35/7.5, NS 35/15, color: gray

Automation > (Knife) disconnect terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Engineered for high-density panel layouts, the Phoenix Contact PT 6-TG disconnect terminal block facilitates secure wire termination and mechanical circuit interruption for demanding industrial control systems.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Connectable conductor cross section solid-core (EF007337): 0.5 mm²
  • Rated current In (EF008250): 20 A
  • Rated voltage (EF000228): 500 V
  • Number of clamp positions per level (EF002660): 2
  • Internally connected stages (EF002661): Yes
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 8.2 mm
  • Height (EF000040): 74.1 mm
  • Depth (EF000049): 42.2 mm
  • Closing plate required (EF002525): No
  • Colour (EF000007): Grey
  • With integrated test socket (EF002547): No

More info

Key Commercial Data

Orderkey3212163
Packing unit50 pc
Minimum order quantity50 pc
Catalog pagePage 107 (C-1-2017)
GTIN4055626394305
Weight per Piece (excluding packing)19.000 g
Custom tariff number85369010
Country of originCN (China)

General

Number of levels1
Number of connections2
Potentials1
Nominal cross section6 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition1.31 W
Maximum load current20 A
Nominal current IN20 A
Nominal voltage UN500 V
Open side panelNo
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.5 mm² / 0.3 kg
6 mm2/ 1.4 kg
10 mm² / 2 kg
Tensile test resultTest passed
Conductor cross section tensile test0.5 mm²
Tractive force setpoint20 N
Conductor cross section tensile test6 mm²
Tractive force setpoint80 N
Conductor cross section tensile test10 mm²
Tractive force setpoint90 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 6,4 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Result of thermal testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 1, class B, body mounted
Test frequencyf1= 5 Hz to f2= 150 Hz
ASD level0.964 (m/s2)2/Hz
Acceleration0.58 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5 g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width8.2 mm
Length74.1 mm
Height42.2 mm
Height NS 35/7,545.3 mm
Height NS 35/1552.8 mm

Connection data

Connection methodPush-in connection
Stripping length10 mm ... 12 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.10 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.8
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.6 mm²
Min. AWG conductor cross section, flexible20
Max. AWG conductor cross section, flexible10
Conductor cross section flexible, with ferrule without plastic sleeve min.0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.6 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.1.5 mm²
Internal cylindrical gageA5

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.