PHOENIX CONTACT MUTTB 2,5-DIO/U-O MUTTB 2,5-DIO/U-O 1066347 PHOENIX CONTACT Terminal block for components, The max. current is determined by t.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MUTTB 2,5-DIO/U-O 1066347 PHOENIX CONTACT Terminal block for components, The max. current is determined by t..

MUTTB 2,5-DIO/U-O

1066347

PHOENIX CONTACT

50 Pcs.

Terminal block for components, The max. current is determined by the diode. Mounted: 1N 4007 diode, reverse voltage: 1300 V, constant limit current: 0.5 A., with integrated diode, rated voltage: 500 V, rated current: 0.5 A, connection type: Screw connection, Sizing cross-section: 2.5 mm², cross-section: 0.2 mm² - 4 mm², mounting: NS 15, NS 35/7.5, NS 35/15, color: gray

Automation > Component terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact MUTTB 2,5-DIO/U-O is a terminal block for components, engineered for high-density space-constrained applications requiring reliable diode integration within control panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product Type: Miniterminal
  • Number of poles: 2
  • Number of connections: 4
  • Number of rows: 2
  • Potential: 2
  • Insulation Properties Surge Category: Iii
  • Degree of pollution: 3
  • Maximum Dissipated Power with Nominal Condition: 0.77 W
  • Number of connections per floor: 2
  • Nominal Section: 2.5 mm²
  • AWG Conductor Section: (Converted according to IEC)
  • Screw thread: M3
  • Peel Length: 7 mm ... 9 mm
  • Male Gauge: A3
  • Standard-compliant connection: IEC 60947-7-1
  • Rigid conductor section: 0.2 mm² ... 4 mm²

More info

▲
Technical data

Notes
GeneralThe max. current is determined by the diode. Mounted: 1N 4007 diode, reverse voltage: 1300 V, constant limit current: 0.5 A.

Item Properties
Product TypeMiniterminal
Number of poles2
Number of connections4
Number of rows2
Potential2
Insulation Properties
Surge CategoryIii
Degree of pollution3

Electrical Properties
Maximum Dissipated Power with Nominal Condition0.77 W

Connection data
Number of connections per floor2
Nominal Section2.5 mm²
AWG Conductor Section(Converted according to IEC)
Screw threadM3
Peel Length7 mm ... 9 mm
Male GaugeA3
Standard-compliant connectionIEC 60947-7-1
Rigid conductor section0.2 mm² ... 4 mm²
AWG Conductor Section24 ... 12 (Converted according to IEC)
Flexible conductor section0.2 mm² ... 2.5 mm²
Flexible Wire Section [AWG]4 ... 14 (Converted according to IEC)
Flexible cable section (toe cap without plastic sleeve)0.25 mm² ... 2.5 mm²
Flexible cable section (toe cap with plastic sleeve)0.25 mm² ... 2.5 mm²
2 conductors with the same cross-section, rigid0.2 mm² ... 1.5 mm²
2 conductors with the same rigid AWG cross-section24 ... 16 (Converted according to IEC)
2 conductors with the same cross-section, flexible0.2 mm² ... 1.5 mm²
2 conductors with the same flexible AWG cross-section24 ... 16 (Converted according to IEC)
2 conductors of equal cross-section, flexible with toe cap, without plastic sleeve0.2 mm² ... 1.5 mm²
Nominal current0.5 A
Maximum Charging Current0.5 A
Nominal voltage500 V
Nominal Section2.5 mm²

Dimensions
Width5.2 mm
Height63.5 mm
Depth50.8 mm
Depth at NS 1550.5 mm
Depth at NS 35/7.552.3 mm
Depth at NS 35/1559.8 mm

Material Data
Colourgrey
Flammability class according to UL 94V0
Insulating material groupI
Insulating materialPA
Static use of cold insulating material-60 °C
Relative Insulating Material Temperature Index (Elec., UL 746 B)130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3
Flammability of NFPA 130 Surfaces (ASTM E 162)approved
NFPA 130 Specific Optical Flue Gas Density (ASTM E 662)approved
NFPA 130 Flue Gas Toxicity (SMP 800C)approved

Electrical Testing
Impulse Voltage Test
Test Voltage Nominal Value7.3 kV
ResultApproved Test
Heating Verification
Heating test requirementTemperature rise ≤ 45 K
ResultApproved Test
Dielectric Strength with Operating Frequency
Test Voltage Nominal Value1.89 kV
ResultApproved Test

Mechanical Properties
Mechanical data
Open sidewallYes

Mechanical testing
Fixing on the bracket
ResultApproved Test

Environmental and life-life conditions
Needle Flame Test
Performance Time30 sec
Broadband Oscillation/Noise
Test SpecificationDIN EN 50155 (VDE 0115-200):2022-06
SpectrumCategory 2 durability test, on the bogie
frequencyf1= 5 Hz to f2= 250 Hz
ASD Level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test DirectionsX, Y, and Z axes
ResultApproved Test
Crash
Test SpecificationDIN EN 50155 (VDE 0115-200):2022-06
Shock TypeSemi-sinusoid
Acceleration30g
Duration of the crash18 ms
Number of collisions per steering3
Test DirectionsX, Y, and Z axes (pos. and neg.)
ResultApproved Test
Environmental conditions
Ambient Temperature (Service)-60 °C ... 105 °C (for max. short-term operating temperature, see RTI Elec.)
Ambient Temperature (Storage/Transport)-25 °C ... 60 °C (for a short time, no more than 24 hours, -60 °C to +70 °C)
Ambient Temperature (Mounting)-5 °C ... 70 °C
Ambient Temperature (Drive)-5 °C ... 70 °C
Permissible air humidity (storage/transport)30 % ... 70 %

Standards & Specifications
Standard-compliant connectionIEC 60947-7-1

assembly
Type of mountingNS 15
NS 35/7.5
NS 35/15

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.