View larger
MT-RS485 2762265 PHOENIX CONTACT Surge protection device
MT-RS485
2762265
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Surge protection device such as the Phoenix Contact MT-RS485 is engineered to protect industrial serial communication buses, including RS-485 interfaces, from destructive transient overvoltages and electrostatic discharge. These DIN rail mounted modules secure data transmission lines in automation networks against induced interference and electrical surges.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2762265
- Packing unit: 5 pc
- Catalog page: Page 100 (TT-2002)
- GTIN: 4017918064945
- Weight per Piece (excluding packing): 101.950 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 77.5 mm
- Width: 47.6 mm
- Depth: 54.9 mm
- Ambient temperature (operation): -40 °C ... 60 °C
- Degree of protection: IP20
- Color: black
- Mounting type: DIN rail: 35 mm
- Type: DIN rail module, one-piece
- Direction of action: Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
More info
▲Key Commercial Data
| Orderkey | 2762265 |
|---|---|
| Packing unit | 5 pc |
| Catalog page | Page 100 (TT-2002) |
| GTIN | 4017918064945 |
| Weight per Piece (excluding packing) | 101.950 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Color | black |
|---|---|
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| VDE requirement class | C2 |
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 12 V DC |
| Rated current | 450 mA (25 °C) |
| Operating effective current ICat UC | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 500 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 22 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 600 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 22 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 600 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 22 V |
| Residual voltage at In(line-line) | ≤ 19 V |
| Residual voltage at In(line-signalground) | ≤ 19 V |
| Voltage protection level Up(line-line) | ≤ 22 V |
| Voltage protection level Up(line-earth) | ≤ 600 V |
| Voltage protection level Up(line-signalground) | ≤ 22 V |
| Response time tA(line-line) | 1 ns |
| Response time tA (line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | |
| ≤ 0.1 dB (up to 10 kHz) | |
| Input attenuation aE, asym. | 0.8 dB (up to 0.1 MHz 50 Ω system) |
| 0.1 dB (up to 10 kHz 600 Ω system) | |
| Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system | 1.3 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 600 Ohm system | 130 kHz |
| Resistance in series | 4.4 Ω |
| Surge protection fault message | none |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |