View larger
ELR H5-IES-PT/500AC-3-IOL 2908669 PHOENIX CONTACT Hybrid motor starter
ELR H5-IES-PT/500AC-3-IOL
2908669
PHOENIX CONTACT
1 Pcs.
Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A hybrid motor starter built by Phoenix Contact under part number ELR H5-IES-PT/500AC-3-IOL provides solid-state switching combined with electromechanical contacts for frequent motor control in automated setups. Reversing starter units of this variety allow seamless directional changes while maintaining robust overload protection in compact enclosures. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Reversing starter
- With short-circuit release (EF006691): No
- Rated control supply voltage DC (EF003980): 19.2 V
- Voltage type for actuating (EF008242): DC
- Rated operation current Ie (EF001443): 3 A
- Rated operation current at AC-3, 400 V (EF009602): 3 A
- Overload release current setting (EF002336): 0.18 A
- Temperature compensated overload protection (EF009604): No
- Release class (EF006668): CLASS 10
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Suitable for rail mounting (EF003972): Yes
- Number of command positions (EF001372): 0
- Suitable for emergency stop (EF001433): Yes
- External reset possible (EF003426): Yes
- Degree of protection (IP) (EF005474): IP20
- Supporting protocol for TCP/IP (EF003050): No
More info
▲Key Commercial Data
| Orderkey | 2908669 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 21 (C-5-2017) |
| GTIN | 4055626321240 |
| Weight per Piece (excluding packing) | 282.700 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Note
| Type of note | Notes on operation |
|---|---|
| Note | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. |
Ambient conditions
| Ambient temperature (operation) | -5 °C ... 55 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Degree of protection | IP20 |
Device supply
| Rated control circuit supply voltage US | 24 V DC |
|---|---|
| Control supply voltage range | 19.2 V DC ... 30 V DC |
| Rated control supply current IS | 65 mA |
| Type of protection | Surge protection |
| Reverse polarity protection |
Input data
| Input name | Enable input |
|---|---|
| Rated actuating voltage UC | 24 V DC |
| Triggering voltage range | 19.2 V DC ... 30 V DC |
| Rated actuating current IC | 7 mA |
| Switching threshold | 9.6 V (“0” signal) |
| 19.2 V (“1” signal) | |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Typical turn-off time | < 30 ms |
Output data load output
| Output name | AC output |
|---|---|
| Rated operating voltage Ue | 500 V AC |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated operating current Ie | 3 A (AC-51) |
| 3 A (AC-53a) | |
| Mains frequency | 50/60 Hz |
| Load current range | 180 mA ... 3 A (see to derating) |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10 |
| Cooling time | 20 min. (for auto reset) |
| Leakage current | 0 mA |
| Type of protection | Surge protection |
General
| Switching frequency | ≤ 2 Hz (Load-dependent) |
|---|---|
| Mounting position | vertical (horizontal DIN rail, motor output below) |
| Mounting type | DIN rail mounting |
| Assembly instructions | alignable, for spacing see derating |
| Operating mode | 100% operating factor |
| Maximum power dissipation | 4.1 W |
| Minimum power dissipation | 0.88 W |
| Operating voltage display | Green LED |
| Status display | Yellow LED |
| Indication | Red LED |
Connection data 1
| Connection name | Control circuits |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Connection data 2
| Connection name | Load circuit |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
UL data
| SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
|---|---|
| 5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) | |
| FLA | 3 A (480 V AC) |
| Group installation | 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded) |
| 30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded) | |
| Category code | NLDX / NRNT |
| Horsepower ratings | 0.5 hp (120 V AC / 208 V AC) |
| 1.5 hp (277 V AC / 480 V AC) |
Insulation characteristics
| Rated insulation voltage | 550 V |
|---|---|
| Rated surge voltage | 6 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Designation | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit |
| Insulation | Safe isolation (IEC 60947-1) |
| Designation | Isolation characteristics between the control input and control supply voltage to auxiliary circuit |
| Insulation | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
| Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | IEC 60947-1 |
| EN 60947-4-2 | |
| IEC 61508 | |
| ISO 13849 |
Approvals/conformities
| Safety Integrity Level according to IEC 61508 | ≤ 3 (Safe shutdown) |
|---|---|
| Category acc. to EN ISO 13849 | ≤ 3 (Safe shutdown) |
| Performance level according to ISO 13849 | e (Safe shutdown) |
| UL certificate | NLDX.E228652 |
| NRNT.E172140 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |