PHOENIX CONTACT PSR-MC37-3NO-1NC-24DC-SP PSR-MC37-3NO-1NC-24DC-SP 2702412 PHOENIX CONTACT Safety relays View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-MC37-3NO-1NC-24DC-SP 2702412 PHOENIX CONTACT Safety relays

PSR-MC37-3NO-1NC-24DC-SP

2702412

PHOENIX CONTACT

1 Pcs.

Safety relays Safety relay for emergency stop and guard doors as well as elevator applications up to SIL 3, cat. 4, PL e, 1 or 2 channel service, automatic or manual start, short circuit detection, 3 trip circuits, US = 24 V DC, plug-in push-in terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact PSR-MC37-3NO-1NC-24DC-SP safety relays are protective switching components utilized in industrial control panels to monitor emergency stop circuits, safety gates, and interlocks, safely interrupting power when a hazard is detected. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Model (EF000010): Basic device
  • Suitable for rail mounting (EF003972): Yes
  • With detachable clamps (EF003340): Yes
  • Type of electric connection (EF003961): Spring clamp connection
  • Suitable for monitoring of position switches (EF007270): Yes
  • Suitable for monitoring of valves (EF007272): No
  • Suitable for monitoring of tactile sensors (EF007271): No
  • Suitable for monitoring of magnetic switches (EF007266): Yes
  • Suitable for monitoring of proximity switches (EF007267): No
  • With start input (EF003342): No
  • With muting function (EF004057): No
  • With feedback circuit (EF003343): Yes
  • Release-delay (EF001129): 0.1 s
  • With approval for BG BIA (EF004145): No
  • With approval according to UL (EF001783): No
  • Width (EF000008): 22.5 mm

More info

▲

Key Commercial Data

Orderkey2702412
Packing unit1 pc
Catalog pagePage 254 (C-6-2017)
GTIN4055626276953
Weight per Piece (excluding packing)202.500 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width22.5 mm
Height117.4 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Power supply

Rated control circuit supply voltage US24 V DC -20 % / +25 %
19.2 V DC ... 30 V DC
Rated control supply current IStyp. 70 mA
Power consumption at UStyp. 1.68 W
Inrush current2 A (Δt = 300 µs at Us)
Protective circuitSurge protection Suppressor diode
Protection against polarity reversal for rated control circuit supply voltage

Digital inputs

Input voltage range "0" signal0 V DC ... 5 V DC (for safe Off; at S12 and S22)
Input current range "0" signal0 mA ... 2 mA (for safe Off; at S12 and S22)
Inrush current< 5 mA (Δt = 500 µs, for Us/Ix at S12)
> -5 mA (Δt = 500 µs, for Us/Ix at S22)
< 10 mA (Δt = 500 µs, for Us/Ix at S35)
Current consumption< 4 mA (with Us/Ixto S12/S22)
< 0.5 mA (with Us/Ixto S35)
Filter timemax. 3 ms (at S12, S22; test pulse width; blanking pulses/dark test)
1 s (at S12, S22; test pulse rate; blanking pulses/dark test)
Where test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width
max. 1 ms (at S12, S22; test pulse width; switch-on pulses/light test)
100 ms (at S12, S22; test pulse rate; switch-on pulses/light test)
Unless switch-on pulses/light tests are safety-related, they should be disabled.
Voltage at input/start and feedback circuit24 V DC -20 % / +25 %

Relay outputs: enabling current path

Output nameEnabling current path
Output descriptionsafety-related N/O contacts
Number of outputs3 (undelayed)
Contact type3 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 5 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Limiting continuous current6 A (observe derating)
Inrush currentmin. 10 mA
max. 6 A
Sq. Total current72 A2(observe derating)
Switching capacitymin. 50 mW
Switching frequency0.5 Hz
Interrupting rating (ohmic load) max.1500 VA (250 V AC, τ = 0 ms)
For additional values, see load curve
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
36 W (60 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
1500 VA (250 V AC, τ = 40 ms)
Mechanical service life10x 106cycles
Switching capacity according to IEC 60947-5-15 A (24 V (DC13))
5 A (250 V (AC15))
Output fuse6 A gL/gG (N/O contact)

Relay outputs: return current/signaling current path

Output nameSignaling current path
Output descriptionnon-safety-related N/C contact
Number of outputs1 (undelayed)
Contact type1 signaling current path
Contact materialAgSnO2
Switching voltagemin. 5 V AC/DC
max. 250 V AC/DC
Limiting continuous current1 A
Inrush currentmin. 10 mA
max. 6 A (Δt = 100 ms)
Sq. Total current1 A2
Switching capacitymin. 50 mW
Switching frequency0.5 Hz
Mechanical service life10x 106cycles
Output fuse1 A gL/gG

Alarm outputs

Output descriptionnon-safety-related
Number of outputs1 (digital)
Voltage23 V DC (Us- 1 V)
Currentmax. 100 mA
Maximum inrush current1 A (Δt = 5 ms at Us)
Short-circuit protectionYes

Times

Typical pickup time at US< 100 ms (when controlled via A1)
Typical response time at US< 100 ms (automatic start)
Typical release time at US< 20 ms (when controlled via A1 or S12)
Restart time< 1 s (Boot time)
Recovery time< 500 ms

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight202.5 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Housing coloryellow
Operating voltage display1 x green LED
Status display3 x green LED

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3
DesignationEN ISO 13849
Performance level (PL)e (5 A DC13; 5 A AC15; 8760 switching cycles/year)
Category4
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 60664-1:2008
Rated insulation voltage250 V AC
250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between all current paths
Basic insulation 4 kV between all current paths and housing
Degree of pollution2
Overvoltage categoryII
Shock15g for Δt = 11 ms (continuous shock: 10g for Δt = 16 ms)
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.