View larger
IB IL AO 4/I/4-20-ECO 2702497 PHOENIX CONTACT Inline terminal
IB IL AO 4/I/4-20-ECO
2702497
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact Inline terminal serves as a modular I/O component within distributed automation networks, connecting field devices to the bus coupler and logic controller. Such output terminals translate controller commands into standard analog current signals to regulate actuators, valves, and variable speed drives. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): Yes
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Resolution of the analogue outputs (EF003577): 12 Bit
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 4
- Analogue outputs configurable (EF008519): No
- Analogue inputs configurable (EF008518): No
More info
▲Key Commercial Data
| Orderkey | 2702497 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 142 (C-6-2017) |
| GTIN | 4055626204499 |
| Weight per Piece (excluding packing) | 84.100 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | 0 °C ... 55 °C (see “Derating” table in the data sheet) |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 84.1 g |
| Note on weight specifications | with connector |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Checksum error I/O error message sent to the bus coupler |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 40 mA |
| max. 50 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 65 mA |
| max. 85 mA | |
| Power consumption | typ. 1.8 W |
Analog outputs
| Number of outputs | 4 |
|---|---|
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded, twisted pair |
| Output name | Analog outputs |
| D/A resolution | 12 bit |
| Type of protection | Short-circuit and overload protection |
| Transient protection | |
| Protective circuit/component | electronic |
| Suppressor diode | |
| Data formats | Standardized representation |
| Representation of output values | 16 bits |
| Process data update | < 10 ms |
| Current output signal | 4 mA ... 20 mA |
| Load/output load current output | < 300 Ω |
| Precision | typ. 0.1 % |
| max. 0.3 % |
Electrical isolation
| Test section | Bus logic (local bus, communications power) 500 V AC 50 Hz 1 min. |
|---|---|
| Analog I/O 500 V AC 50 Hz 1 min. | |
| Functional earth ground 500 V AC 50 Hz 1 min. |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |