View larger
EMD-SL-PTC 2866093 PHOENIX CONTACT Monitoring relay
EMD-SL-PTC
2866093
PHOENIX CONTACT
1 Pcs.
Automation > Temperature monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact part number EMD-SL-PTC is a specialized monitoring relay designed to protect equipment from excessive temperatures. Such relays continuously check sensor inputs from motor windings or industrial systems and trigger safety actions when limits are exceeded. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Temperature monitoring relay
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Article revision: 02
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: III
- Pollution degree: 2
- Service life electrical: 2x 10 5 cycles at ohmic load, 1000 VA
- Rated insulation voltage: 300 V
- Rated surge voltage: 4 kV
- Supply Supply voltage range: 24 V AC ... 230 V AC (see Power modules)
- Nominal power consumption: 2 VA (1.5 W)
- Input name: Measuring input
- Maximum input voltage: 7.5 V DC (connection terminal blocks: T1 and T2)
- Frequency range: 50 Hz ... 60 Hz
More info
▲| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Temperature monitoring relay |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Article revision | 02 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Service life electrical | 2x 105cycles at ohmic load, 1000 VA |
| Rated insulation voltage | 300 V |
| Rated surge voltage | 4 kV |
| Supply | |
| Supply voltage range | 24 V AC ... 230 V AC (see Power modules) |
| 24 V DC (see Power modules) | |
| Nominal power consumption | 2 VA (1.5 W) |
| Input name | Measuring input |
| Maximum input voltage | 7.5 V DC (connection terminal blocks: T1 and T2) |
| Frequency range | 50 Hz ... 60 Hz |
| Maximum temperature coefficient | < 0.1 %/K |
| Response value | ≥ 3.6 kΩ (Relay drops out) |
| Function | Winding temperature monitoring |
| Basic accuracy | ± 10 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Total cold resistance | < 1.5 kΩ |
| Release value | ≤ 1.8 kΩ (Relay picks up) |
| Short-circuit detection | < 20 Ω |
| Voltage influence | ≤ 1 % |
| Recovery time | 500 ms |
| Control | |
| Connection name | Connection of an external reset button (floating controlled N/O contact) |
| Load capacity | Cannot carry load |
| Cable length | max. 10 m |
| Switching | |
| Contact switching type | 2 floating changeover contacts |
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Width | 22.5 mm |
| Height | 90 mm |
| Depth | 113 mm |
| Color | green (RAL 6021) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Ambient conditions | |
| Degree of protection (Housing) | IP40 (Housing) |
| Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Permissible humidity (operation) | 15 % ... 85 % |
| CE | |
| Certificate | CE-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Noise immunity | EN 61000-6-2 |
| Noise emission | EN 61000-6-3 |
| Standards/regulations | EN 50178 |
| Mounting type | DIN rail mounting |
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting position | any |