View larger
EMD-SL-V-UV-300 2866035 PHOENIX CONTACT Monitoring relay
EMD-SL-V-UV-300
2866035
PHOENIX CONTACT
1 Pcs.
Automation > Voltage monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
EMD-SL-V-UV-300 2866035 PHOENIX CONTACT Monitoring relay serves as an essential protective element in electrical architectures, designed to detect and respond to undesirable voltage variations. These units provide reliable signal switching to safeguard valuable industrial equipment against electrical faults.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- With detachable clamps (EF003340): No
- Type of voltage measuring range (EF003399): AC/DC
- Response value voltage (EF008193): 0 V
- Single-phase under voltage possible (EF003390): Yes
- Three-phase under voltage possible (EF003391): No
- Single-phase over voltage possible (EF003392): No
- Three-phase over voltage possible (EF003393): No
- Single-phase hysteresis possible (EF003394): No
- Three-phase hysteresis possible (EF003395): No
- Contains function DC-under voltage (EF003396): No
- Contains function DC-over voltage (EF003397): No
- Contains function DC-voltage hysteresis (EF003398): No
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 1
More info
▲Key Commercial Data
| Orderkey | 2866035 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 267 (C-5-2017) |
| GTIN | 4017918924331 |
| Weight per Piece (excluding packing) | 132.300 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Input voltage range | 0 V ... 30 V AC/DC (connection terminal blocks: U1 and GND) |
|---|---|
| 0 V ... 60 V AC/DC (connection terminal blocks: U2 and GND) | |
| 0 V ... 300 V AC/DC (connection terminal blocks: U3 and GND) | |
| Maximum temperature coefficient | < 0.1 %/K |
| Function | Undervoltage |
| Min. setting range | 5 % ... 95 % (From UN) |
| Max. setting range | 10 % ... 100 % (From UN) |
| Setting range for response delay | 0.2 s ... 10 s |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Recovery time | 500 ms |
Contact side
| Contact type | 1 floating PDT |
|---|---|
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
General
| Mechanical service life | approx. 2x 107cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Overvoltage category | III, basic insulation (as per EN 50178) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Color | green |
| Rated insulation voltage | 300 V (acc. to EN 50178) |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Connection data
| Conductor cross section flexible min. | 0.25 mm² |
|---|---|
| Conductor cross section flexible max. | 2.5 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Tightening torque | 1 Nm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
|---|---|
| Noise emission | EN 61000-6-3 |
| Noise immunity | EN 61000-6-2 |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Conformance | CE-compliant |
| UL, USA/Canada | UL/C-UL listed UL 508 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |