View larger
EMD-SL-C-UC-10 2867937 PHOENIX CONTACT Monitoring relay
EMD-SL-C-UC-10
2867937
PHOENIX CONTACT
1 Pcs.
Automation > Current monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Keep a close watch on system variables with the Phoenix Contact EMD-SL-C-UC-10. Monitoring relays are standard components in industrial switchgear, providing vital feedback and tripping signals to protect valuable electrical equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Current monitoring relay
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Article revision: 02
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: III
- Pollution degree: 2
- Service life electrical: 2x 10 5 cycles at ohmic load, 1000 VA
- Mains type: 1-phase
- Rated insulation voltage: 300 V
- Rated surge voltage: 4 kV
- Supply Supply voltage range: 24 V AC ... 230 V AC (see Power modules)
- Nominal power consumption: 2 VA (1.5 W)
- Input name: Measuring input
- Measured value: DC, AC sine
- Input current range: 0 mA ... 100 mA (Connection terminals: I1 and GND)
More info
▲| Product type | Current monitoring relay |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Article revision | 02 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Service life electrical | 2x 105cycles at ohmic load, 1000 VA |
| Mains type | 1-phase |
| Rated insulation voltage | 300 V |
| Rated surge voltage | 4 kV |
| Supply | |
| Supply voltage range | 24 V AC ... 230 V AC (see Power modules) |
| 24 V DC (see Power modules) | |
| Nominal power consumption | 2 VA (1.5 W) |
| Input name | Measuring input |
| Measured value | DC, AC sine |
| Input current range | 0 mA ... 100 mA (Connection terminals: I1 and GND) |
| 0 A ... 1 A (Connection terminals: I2 and GND) | |
| 0 A ... 10 A (Connection terminals: I3 and GND) | |
| Overload capacity | 800 mA (at IN= 100 mA) |
| 3 A (at IN= 1 A) | |
| 12 A (at IN= 10 A) | |
| Input resistance current input | 470 mΩ (at IN= 100 mA) |
| 47 mΩ (at IN= 1 A) | |
| 5 mΩ (at IN= 10 A) | |
| Frequency range | 48 Hz ... 63 Hz |
| Maximum temperature coefficient | < 0.1 %/K |
| Setting range for response delay | 0.2 s ... 10 s |
| Min. setting range | 5 % ... 95 % (from IN) |
| Max. setting range | 10 % ... 100 % (from IN) |
| Function | Undercurrent |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Recovery time | 500 ms |
| Switching | |
| Contact switching type | 1 floating changeover contact |
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Width | 22.5 mm |
| Height | 90 mm |
| Depth | 113 mm |
| Color | green (RAL 6021) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Ambient conditions | |
| Degree of protection (Housing) | IP40 (Housing) |
| Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Permissible humidity (operation) | 15 % ... 85 % |
| CE | |
| Certificate | CE-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Noise immunity | EN 61000-6-2 |
| Noise emission | EN 61000-6-3 |
| Standards/regulations | EN 50178 |
| Mounting type | DIN rail mounting |
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting position | any |