View larger
EMD-FL-V-300 2866048 PHOENIX CONTACT Monitoring relay
EMD-FL-V-300
2866048
PHOENIX CONTACT
1 Pcs.
Automation > Voltage monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact monitoring relay (part number EMD-FL-V-300) serves as an essential protective component in industrial control panels, designed to continuously track electrical parameters and safeguard connected equipment from potentially damaging voltage fluctuations. These devices are widely deployed across manufacturing and automation systems to trigger corrective actions or shutdowns when voltage levels stray outside of safe operating thresholds.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Voltage monitoring relay
- Operating mode: 100% operating factor
- Mechanical service life: approx. 2x 10 7 cycles
- Data management status Article revision: 03
- Insulation characteristics Insulation: Basic insulation
- Overvoltage category: III
- Pollution degree: 2
- Service life electrical: 2x 10 5 cycles at ohmic load, 1000 VA
- Maximum power dissipation for nominal condition: 1 W
- Mains type: 1-phase
- Rated insulation voltage: 300 V
- Rated surge voltage: 4 kV
- Supply Supply voltage range: 24 V AC ... 240 V AC -15 % ... +10 %
- Type of supply voltage: AC/DC
- Nominal power consumption: 4.5 VA (1.5 W)
More info
▲| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Voltage monitoring relay |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Data management status | |
| Article revision | 03 |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
| Service life electrical | 2x 105cycles at ohmic load, 1000 VA |
| Maximum power dissipation for nominal condition | 1 W |
| Mains type | 1-phase |
| Rated insulation voltage | 300 V |
| Rated surge voltage | 4 kV |
| Supply | |
| Supply voltage range | 24 V AC ... 240 V AC -15 % ... +10 % |
| 24 V DC ... 240 V DC -20 % ... +25 % | |
| Type of supply voltage | AC/DC |
| Nominal power consumption | 4.5 VA (1.5 W) |
| Input name | Measuring input |
| Measured value | DC, AC sine |
| Protection | ≤ 20 A |
| Input voltage range | 0 V ... 30 V AC/DC (connection terminal blocks: U1 and GND) |
| 0 V ... 60 V AC/DC (connection terminal blocks: U2 and GND) | |
| 0 V ... 300 V AC/DC (connection terminal blocks: U3 and GND) | |
| Maximum input voltage | 100 Vrms(connection terminal blocks: U1 and GND) |
| 150 Vrms(connection terminal blocks: U2 and GND) | |
| 440 Vrms(connection terminal blocks: U3 and GND) | |
| Input resistance of voltage input | 47 kΩ (connection terminal blocks: U1 and GND) |
| 100 kΩ (connection terminal blocks: U2 and GND) | |
| 470 kΩ (connection terminal blocks: U3 and GND) | |
| Frequency range | 48 Hz ... 400 Hz |
| Maximum temperature coefficient | < 0.1 %/K |
| Setting range for response delay | 0.1 s ... 10 s |
| Setting range for starting delay | 0 s ... 10 s |
| Min. setting range | 5 % ... 95 % (From UN) |
| Max. setting range | 10 % ... 100 % (From UN) |
| Function | Undervoltage |
| Overvoltage | |
| Window | |
| Error memory | |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Recovery time | 500 ms |
| Switching | |
| Contact switching type | 2 floating changeover contacts |
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.25 mm² ... 2.5 mm² |
| Conductor cross section AWG | 20 ... 14 |
| Width | 22.5 mm |
| Height | 90 mm |
| Depth | 113 mm |
| Color | green (RAL 6021) |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Ambient conditions | |
| Degree of protection (Housing) | IP40 (Housing) |
| Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| -25 °C ... 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Permissible humidity (operation) | 15 % ... 85 % |
| CE | |
| Certificate | CE-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 508 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Noise immunity | EN 61000-6-2 |
| Noise emission | EN 61000-6-4 |
| Standards/regulations | EN 50178 |
| Mounting type | DIN rail mounting |
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting position | any |