PHOENIX CONTACT EMD-FL-3V-400 EMD-FL-3V-400 2866064 PHOENIX CONTACT Monitoring relay View larger
Images are for illustrative purposes only. Please refer to data sheet for details

EMD-FL-3V-400 2866064 PHOENIX CONTACT Monitoring relay

EMD-FL-3V-400

2866064

PHOENIX CONTACT

1 Pcs.

Monitoring relay Supervisory relay for 3-phase voltage monitoring of 280...520 V AC, undervoltage, Window, phase sequence, phase fault, asymmetry, long-range power supply, 2 switched contacts

Automation > Voltage monitoring relay
Industrial Relays

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Supervise three-phase power networks effectively using the Phoenix Contact EMD-FL-3V-400 monitoring relay. Monitoring relays play a crucial role in electrical protection schemes by providing continuous supervision of critical line parameters to prevent equipment damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Type of electric connection (EF003961): Screw connection
  • With detachable clamps (EF003340): No
  • Voltage measuring range 1 (EF006134): 280 V
  • Type of voltage measuring range (EF003399): AC
  • Single-phase under voltage possible (EF003390): No
  • Three-phase under voltage possible (EF003391): Yes
  • Single-phase over voltage possible (EF003392): No
  • Three-phase over voltage possible (EF003393): No
  • Single-phase hysteresis possible (EF003394): No
  • Three-phase hysteresis possible (EF003395): Yes
  • Contains function DC-under voltage (EF003396): No
  • Contains function DC-over voltage (EF003397): No
  • Contains function DC-voltage hysteresis (EF003398): No
  • Number of contacts as normally closed contact (EF008255): 0
  • Number of contacts as normally open contact (EF008256): 0
  • Number of contacts as change-over contact (EF008257): 2

More info

▲

Key Commercial Data

Orderkey2866064
Packing unit1 pc
Catalog pagePage 268 (C-5-2017)
GTIN4017918975029
Weight per Piece (excluding packing)164.000 g
Custom tariff number85364900
Country of originAT (Austria)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width22.5 mm
Height90 mm
Depth113 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)-25 °C ... 70 °C

Input data

Nominal input voltage UN3 N ~ 400/230 V
Maximum temperature coefficient< 0.1 %/K
FunctionUndervoltage, window, asymmetry, phase sequence, phase failure
Min. setting range-30 % ... 20 % (From UN)
Max. setting range-20 % ... 30 % (From UN)
Min setting range of the voltage threshold value280 V AC ... 480 V AC
Max. setting range of the voltage threshold value320 V AC ... 520 V AC
Setting range for response delay0.1 s ... 10 s
Basic accuracy± 5 % (of scale end value)
Setting accuracy≤ 5 % (of scale end value)
Repeat accuracy≤ 2 %
Asymmetry5 % ... 25% / OFF
Recovery time500 ms

Contact side

Contact type2 floating PDT contacts
Maximum switching voltage250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse5 A (fast-blow)

Power supply

Supply voltage230 V AC
24 V DC
Supply voltage range24 V AC ... 240 V AC -15 % ... +10 %
24 V DC ... 240 V DC -20 % ... +25 %

General

Mechanical service lifeapprox. 2x 107cycles
Operating mode100% operating factor
Mounting positionany
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibilityConformance with EMC directive
Overvoltage categoryIII, basic insulation (as per EN 50178)
Housing insulation materialPolyamide PA, self-extinguishing
Colorgreen
Rated insulation voltage300 V (acc. to EN 50178)
ConformanceCE-compliant
UL, USA/CanadaUL/C-UL listed UL 508

Connection data

Conductor cross section flexible min.0.25 mm²
Conductor cross section flexible max.2.5 mm²
Connection methodScrew connection
Stripping length8 mm
Conductor cross section solid0.5 mm² ... 2.5 mm²
Conductor cross section flexible0.25 mm² ... 2.5 mm²
Conductor cross section AWG20 ... 14
Tightening torque1 Nm

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2
Low Voltage DirectiveConformance with Low Voltage Directive
ConformanceCE-compliant
UL, USA/CanadaUL/C-UL listed UL 508

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.